DESCRIPTIOn:
Thyro-A/Thyro-AX
Thyro-S
Thyro-S, Thyro-A and Thyro-AX
LEDs
RELAy*
LEDs
RELAy*
frequency measurement outside
of 47 hz to 63 hz
Bit0
Pulse Inhibit LED
flashes slowly
dropped out
Test LED flashes slowly
dropped out
SynC error, no zero crossing within
the gate
Bit1
Pulse Inhibit LED
flashes slowly
dropped out
Test LED flashes slowly
dropped out
Temperature monitoring triggered Bit2
Load fault LED
flashes slowly
dropped out
Load Fault flashes slowly
dropped out
Load error
Bit3
Load fault LED on
dropped out
Load fault on
dropped out
flash values invalid
Bit4
Pulse Inhibit LED and Load
Fault LED flash fast simulta
-
neously
dropped out
Test LED a. Load fault LED
flash fast simultaneously
dropped out
Mains Undervoltage
(< AD_P_SPG_MIn)
Bit5
Pulse Inhibit LED,
Load fault LED a.
Test-LED on
dropped out
Load fault LED and
Test LED on
dropped out
Mains Overvoltage
(> AD_P_SPG_MAX)
Bit6
none
energised
none
energised
Master/Slave error (only with 2A)
Bit8
none
energised
only with Thyro-A/Thyro-AX
---
Undervoltage Limit
Bit9
none
energised
only with Thyro-A/Thyro-AX
---
Overvoltage Limit
Bit10 none
energised
only with Thyro-A/Thyro-AX
---
Undercurrent Limit
Bit11 none
energised
only with Thyro-A/Thyro-AX
---
Overcurrent Limit
Bit12 none
energised
only with Thyro-A/Thyro-AX
---
Low Power Limit
Bit13 none
energised
only with Thyro-A/Thyro-AX
---
high Power Limit
Bit14 none
energised
only with Thyro-A/Thyro-AX
---
TAB. 9 A ERROR fLAGS (ERROR)
4.5 STATUS AnD ERROR COMMUnICATIOn
* The table only shows the default configuration of the relay function.
It can be configured by Thyro-Tool family, which message shall be shown by
the relay an which not.
The relay only exists in h RL1, h RLP1, h RL2 or h RLP2 device, not in the h1