Response:
ADDRESS
fUnCTIOn
ERROR CODE
CRC
100
131
2
208, 238
If more than 120 registers are requested simultaneously the Exception
Response „ILLEGAL DATA VALUE” is transmitted (see Chapt. 4.3.5).
Response:
ADDRESS
fUnCTIOn
ERROR CODE
CRC
100
131
3
17, 46
4.3.2 PRESET SInGLE REGISTER (0X06)
With this telegram the master can change a register (function code 0x06).
Example:
Registers 6 + 256 (operating mode Thyro-A/Thyro-AX, Controller 2)
are to be changed to 2 (VAR) in the bus module with the address 100
(1 overflow into high byte).
Inquiry:
ADDRESS
fUnCTIOn
REGISTER
DATA
CRC
100
6
1, 6
0, 2
224, 3
Response:
ADDRESS
fUnCTIOn
REGISTER
DATA
CRC
100
6
1, 6
0, 2
224, 3
Error:
Should the register’s address lie outside the address location or is
an attempt made to write on an address that cannot be changed, the
Exception Response responds by transmitting „ILLEGAL DATA
ADDRESS” (see Chapt. 4.3.5). This is also the case if the controller in
question is not connected!
Response:
ADDRESS
fUnCTIOn
ERROR CODE
CRC
100
134
2
211, 190