Communication Interfaces
4-41
HFV 8000 Generator
CONTROL PANEL ROTARY SWITCHES
The DeviceNet control panel features three rotary switches to set the network address
and communication data rate. Each time the DeviceNet interface is energized the
switch settings are read by the DeviceNet master. Figure 4-13 provides an illustration
of these switches.
Data Rate Rotary Switch
Use the
DATA RATE
switch to select a communication baud rate:
• 0 = 125 kbits per second
• 1 = 250 kbits per second
• 2 = 500 kbits per second
The default is 500 kbits/s. A switch setting in the
PGM
region allows the DeviceNet
master to set the baud rate for the unit.
Note:
If your power supply is configured with two DeviceNet cards, it is important
that you set the
DATA RATE
for
both
cards to the same setting as the
DeviceNet network setting. Any card not set to the network setting will fault
when the network is brought up.
Node Address Rotary Switches
Use the
NODE ADDRESS
rotary switches,
MSD
(most significant digit) and
LSD
(least significant digit), to select the DeviceNet network address (MAC ID). MAC IDs
0 through 63 are valid. Use the
MSD
switch to select the MAC ID’s most significant
digit; use the
LSD
switch to select the MAC ID’s least significant digit. Switch
settings greater than 63 (or in the
PGM
region of the
MSD
switch) allow you to set
the MAC ID through the DeviceNet master.
If your power supply is configured with two DeviceNet cards, it is important that you
set the combined NODE ADDRESS of the first card to a different setting than the
combined NODE ADDRESS of the second card. If you fail to do this, one side will
fault when the network is brought up.
DeviceNet™ Interface Information and Supported Features
The Advanced Energy HFV generator operates as a GROUP 2 slave device on a
DeviceNet network. The unit supports explicit messages and polled I/O messages of
the predefined master/slave connection set. The Advanced Energy DeviceNet
interface does
not
support the explicit unconnected message manager (UCMM).
The DeviceNet interface responds to poll requests in less than one millisecond (<1 ms
poll response time). Explicit requests are serviced in under two millisecond (<2 ms
explicit response time).
Содержание HFV 8000
Страница 1: ...HFV 8000 Generator 2 MHz 208 V Input with DeviceNet March 2004 5705211 C User Manual...
Страница 2: ......
Страница 3: ...User Manual HFV 8000 Generator 2 MHz 208 V Input with DeviceNet 5705211 C...
Страница 6: ...iv 5705211 C Advanced Energy...
Страница 14: ...xii 5705211 C Advanced Energy...
Страница 22: ...1 8 Safety and Product Compliance Guidelines 5705211 C Advanced Energy...
Страница 26: ...2 4 Product Overview and Theory 5705211 C Advanced Energy...
Страница 36: ...3 10 Product Specifications 5705211 C Advanced Energy...
Страница 94: ...4 58 Communication Interfaces 5705211 C Advanced Energy...
Страница 97: ...5705211 C Installation Setup and Operation 5 3 HFV 8000 Generator Front Panel Drawing Figure 5 1 Front view...
Страница 114: ...5 20 Installation Setup and Operation 5705211 C Advanced Energy...
Страница 128: ...6 14 Troubleshooting and Global Customer Support 5705211 C Advanced Energy...
Страница 132: ...iv 5705211 C Advanced Energy...
Страница 134: ...5705211 C ii HFV 8000 Generator...
Страница 140: ...5705211 C viii HFV 8000 Generator...
Страница 141: ...ix 5705211 C Advanced Energy...
Страница 142: ...Index x 5705211 C Advanced Energy...