ELECTRICAL CONNECTIONS continued

Check after installation 

 

   Polarity 

   Short circuit 

   Earth continuity 

   Resistance to earth 

   Visual check for stray wiring strands etc 

   Mechanical check for integrity of connections 

 

Do not switch on until the unit is full of water and air has been purged from the system. 

 

IMPORTANT

 

 

The switching in the boiler is zero voltage and cannot be used for mains switching e.g. three 
port valves. 

 

We recommend hot water is provided by an independent electric/solar cylinder for 
optimum efficiency.

COMMISSIONING

Fill the system by opening isolating valves to the feed and expansion tank or to the filling 
loop of a sealed system. Charge sealed systems from 0.75 bar to 1 bar. 

 

When the system is full, and has been thoroughly checked for leaks it should be flushed 
out to remove any debris. 

 

Refill, add system cleanser and switch on the boiler. 

 

The boiler controls are fully automatic. The LED will turn green showing that the boiler is 
powered up and awaiting demand. When heating demand is on (set the programmer and 
room thermostat to call for demand) the pump will be energised for 5 seconds in order 
for the flow switch to sense flow in the boiler. If it does not sense flow the boiler will switch 
off, the LED will show red (continuously) indicating that the circuit contains air (no flow). 
Check that all air is purged and try again. The boiler can be switched back on again by 
turning the programmer/room thermostat off and on. It is usual for this process to take a 
little time in all heating circuits. 

 

TIP:

 

Run the boiler with pods disconnected until air is purged. You may need to increase the 
pump speed to do this. 

 

NEVER link the flow switch out – it is dangerous and will damage the heater pods. This 
action will void guarantees. 

 

Allow the boiler to run for 30 minutes to ensure that it is operating correctly and flush 
again. 

 

Refill the system adding inhibitor following manufacturer’s instructions and switch on.

Содержание EG 12

Страница 1: ...INSTALLATION AND USER GUIDE 6 9 12kW ELECTRIC BOILER PLEASE RETAIN FOR REFERENCE ISSUE 2 1220...

Страница 2: ...eGlow is controlled externally with a programmer and room thermostat arrangement with voltage free switching not supplied There is a connector in the boiler casing for this purpose Standard central he...

Страница 3: ...TAGE 90 95 C 90 95 C 90 95 C NOM HEAT OUTPUT 20 000 BTU 30 000 BTU 40 000 BTU AUTO AIR VENT FITTED FITTED FITTED FLOW SWITCH FITTED FITTED FITTED AUTO BY PASS FITTED FITTED FITTED MIN PRESSURE COLD FI...

Страница 4: ...on if an indirect cylinder is to be installed Advance recommend an Advance Appliances stainless steel pre plumbed unvented cylinder and would always advise customers to consider renewable energy such...

Страница 5: ...a double pole RCD capable of breaking the full current load Remember that the full house loading must be taken into consideration when calculating mains demand Refer to IEE regulations for wiring size...

Страница 6: ...boiler controls are fully automatic The LED will turn green showing that the boiler is powered up and awaiting demand When heating demand is on set the programmer and room thermostat to call for deman...

Страница 7: ...D may flash red indicating overheat The unit is protected by the PCB controller in addition to a thermomechanical device The appliance will reset itself when it cools If the overheat recurs please ens...

Страница 8: ...8 SCHEMATIC AUTO AIR VENT HIGH LIMIT THERMOSTATS THERMISTER RETURN CONTACTOR MAINS FLOW SWITCH 3 KW PODS A RATED PUMP FLOW AUTO BYPASS CONTROL PCB...

Страница 9: ...e to ensure the voltage does not go below the minimum level Yes No Check voltage input R H contactor Yes No Go back to source and check wiring Faulty wires from block to contactor Check ZERO voltage d...

Страница 10: ...there should be con nuity Yes No Ensure system is fully purged of air If yes replace ow switch Disconnect all pods Turn on the boiler Check each of the pod leads in pairs for power note that the pods...

Страница 11: ...E IS 21 OHMS Mode SW1 SW2 SW3 SW4 Central hea ng O X X X Under oor On X X X 3KW X O O X 6KW X O On X 9KW X On O X 12KW X On On X Enable main contactor X X X On Disable main contactor X X X O Connect e...

Страница 12: ...stallation date Warranty is registered on Advance Appliances Website It is installed correctly and the benchmark paperwork is completed It is used for its intended purpose It is operated properly It h...

Отзывы: