EGLOW PROBLEM SOLVING continued

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check connuity on 

buon stat(s) on pods 

Yes 

No 

Replace buon stat(s) 

Is the pump running? 

Yes 

No 

Check voltage to pump  

No 

Power 

Power 

Replace 

board 

Replace 

pump 

Test flow switch with the pump 

running, there should be 

connuity  

Yes 

No 

Ensure system is fully purged 

of air. If yes, replace flow 

switch  

Disconnect all pods. Turn on the boiler. Check 

each of the pod leads in pairs for power – note 

that the pods come on in sequences, not all at 

once 

Yes 

No 

Replace board  

 

Disconnect all pods, check for connuity 

across terminals, check resistances are 18-21Ω 

and check for earth leakages between the pod 

terminal and pod case 

Yes 

No 

Replace pod 

Содержание EG 12

Страница 1: ...INSTALLATION AND USER GUIDE 6 9 12kW ELECTRIC BOILER PLEASE RETAIN FOR REFERENCE ISSUE 2 1220...

Страница 2: ...eGlow is controlled externally with a programmer and room thermostat arrangement with voltage free switching not supplied There is a connector in the boiler casing for this purpose Standard central he...

Страница 3: ...TAGE 90 95 C 90 95 C 90 95 C NOM HEAT OUTPUT 20 000 BTU 30 000 BTU 40 000 BTU AUTO AIR VENT FITTED FITTED FITTED FLOW SWITCH FITTED FITTED FITTED AUTO BY PASS FITTED FITTED FITTED MIN PRESSURE COLD FI...

Страница 4: ...on if an indirect cylinder is to be installed Advance recommend an Advance Appliances stainless steel pre plumbed unvented cylinder and would always advise customers to consider renewable energy such...

Страница 5: ...a double pole RCD capable of breaking the full current load Remember that the full house loading must be taken into consideration when calculating mains demand Refer to IEE regulations for wiring size...

Страница 6: ...boiler controls are fully automatic The LED will turn green showing that the boiler is powered up and awaiting demand When heating demand is on set the programmer and room thermostat to call for deman...

Страница 7: ...D may flash red indicating overheat The unit is protected by the PCB controller in addition to a thermomechanical device The appliance will reset itself when it cools If the overheat recurs please ens...

Страница 8: ...8 SCHEMATIC AUTO AIR VENT HIGH LIMIT THERMOSTATS THERMISTER RETURN CONTACTOR MAINS FLOW SWITCH 3 KW PODS A RATED PUMP FLOW AUTO BYPASS CONTROL PCB...

Страница 9: ...e to ensure the voltage does not go below the minimum level Yes No Check voltage input R H contactor Yes No Go back to source and check wiring Faulty wires from block to contactor Check ZERO voltage d...

Страница 10: ...there should be con nuity Yes No Ensure system is fully purged of air If yes replace ow switch Disconnect all pods Turn on the boiler Check each of the pod leads in pairs for power note that the pods...

Страница 11: ...E IS 21 OHMS Mode SW1 SW2 SW3 SW4 Central hea ng O X X X Under oor On X X X 3KW X O O X 6KW X O On X 9KW X On O X 12KW X On On X Enable main contactor X X X On Disable main contactor X X X O Connect e...

Страница 12: ...stallation date Warranty is registered on Advance Appliances Website It is installed correctly and the benchmark paperwork is completed It is used for its intended purpose It is operated properly It h...

Отзывы: