EGLOW PROBLEM SOLVING continued
10
Check connuity on
buon stat(s) on pods
Yes
No
Replace buon stat(s)
Is the pump running?
Yes
No
Check voltage to pump
No
Power
Power
Replace
board
Replace
pump
Test flow switch with the pump
running, there should be
connuity
Yes
No
Ensure system is fully purged
of air. If yes, replace flow
switch
Disconnect all pods. Turn on the boiler. Check
each of the pod leads in pairs for power – note
that the pods come on in sequences, not all at
once
Yes
No
Replace board
2
Disconnect all pods, check for connuity
across terminals, check resistances are 18-21Ω
and check for earth leakages between the pod
terminal and pod case
Yes
No
Replace pod