61213075L2-5E

Issue 5, February 2011

    3

Compliance

Table 1

 shows the compliance codes for the NIU3 PM. 

The NIU3 PM is NRTL listed to the applicable UL 
standards. 

This device complies with Part 15 of the FCC rules. 
Operation is subject to the following two conditions: 

1. This device may not cause harmful interference.
2. This device must accept any interference received, 

including interference that may cause undesired 
operation.

Changes or modifications not expressly approved by 
ADTRAN could void the user’s authority to operate this 
equipment.

This product is intended for installation in a DC-C 
(common) bonding and grounding system only. It is not 
intended or designed for installation in a DC-I (isolated) 
bonding and grounding system.

2. INSTALLATION

After unpacking the NIU3 PM inspect it for damage. If 
damage is noted, file a claim with the carrier, then 
contact ADTRAN. For more information, refer to the 

Warranty and Customer Service

 section.

This product is intended for use in a restricted access 
area in a type “B” or “E” enclosure only.

Location

The NIU3 PM installs at any convenient location 
adjacent to the customer. The NIU3 PM can pass both 
network and customer signals up to 900 feet. If total 
transmission distance exceeds 900 feet, DS3 data may 
cease during NIU3 bypass operations. The DS3 NIU is 
not intended for use as a repeater. See 

Figure 2

 on page 

2 for maximum recommended transmission distances.

The NIU3 PM inserts into the host circuit board of the 
standalone housing or the backplane edge connector on 
either of the shelf units. Card guides direct the unit for 
correct insertion and prevent perpendicular movement. 
The unit is secured with two front panel thumbscrews.

Jack Connections

The three housings each have four rear panel BNC 
connectors for each NIU3 PM:

• Two for Customer Receive/Transmit
• Two for Network Receive/Transmit

Two additional mid-size jacks on the NIU3 PM front 
panel provide a nonintrusive monitoring point for the 
transmit network and customer signals. The front panel 
DB-9 provides an RS-232 craft interface. The 
standalone housing or shelf security panel must be 
opened to access the monitoring jacks and the RS-232 
craft interface.

Housing Ground Option

CAUTION

Terminate grounds to an approved ground 
location. Check metal-to-metal contact on all 
ground connections, and verify ground circuit 
continuity.

Optionally, frame ground is provided by ground posts 
on the standalone chassis. The ground posts and 

TB1

 are 

electrically connected. A ground wire portal on the rear 
panel of the housing provides access for grounding via 

TB1

. The ground posts are installed on the standalone 

housing, the 3-slot shelf, and the 12-slot shelf rear 
panels. A 6 AWG (maximum) ground lug is included 
with each chassis for connecting the ground wire to the 
ground posts.

Shelf Power

The NIU3 PM operates on local ±24 VDC or –48 VDC. 
The standalone housing, 3-slot, and 12-slot shelf 
backplanes have a dual power terminal (

TB1

) with 

terminal connections for 

PWR A

RET

 

and 

PWR B

RET

 

wiring (18 AWG minimum) plus a common 

Frame Ground (18 AWG minimum) connection (see 

Figure 3 

on page 4). The standalone housing has a 

power wire portal on the rear panel for termination on 
the host circuit board at 

TB1

.

Table 1.  Compliance Codes

Code

Input

Output

Power Code (PC)

F

C

Telecommunication Code (TC)

Installation Code (IC)

A

C A U T I O N ! 

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

Содержание DS3 NIU3 PM

Страница 1: ...nce History 18 Figure 19 Performance Thresholds Screen 19 Figure 20 Change Performance Threshold Screen 19 Figure 21 Performance History Data Definitions 1 20 Figure 22 Performance History Data Defini...

Страница 2: ...ntinuity to maintain data flow between the network and the customer A front panel LED on the NIU3 PM provides notification of failure Figure 2 illustrates a circuit diagram of the NIU3 PM in a SONET b...

Страница 3: ...ndicular movement The unit is secured with two front panel thumbscrews Jack Connections The three housings each have four rear panel BNC connectors for each NIU3 PM Two for Customer Receive Transmit T...

Страница 4: ...ormer is specifically intended for use with the standalone housing P N 1212070L1 For the AC DC transformer the red power wire is connected to the RET terminal and the black return wire to the PWR term...

Страница 5: ...LOS AIS Red Amber On On Off DS3 signal not present at network interface AIS present at network interface DS3 signal present at network interface NTWK C BIT Green Amber On Off On C Bit framing detecte...

Страница 6: ...itting RAI towards the network If there is no signal from the customer the CUST LOS AIS LED turns on red and the NIU3 PM will transmit the signal selected by the Customer LOS option on the Provisionin...

Страница 7: ...nd AIS RAI when LOF detected Enabled then RAI is transmitted to the Network Interface AIS detected on Network Interface Network Interface to Customer Interface AIS is transparently passed through to t...

Страница 8: ...ing in misplaced characters or screen time outs NOTE Not all option screens are shown in this document Many screen options selected will advance to additional screens with additional options Navigatio...

Страница 9: ...tect valid frame alignment in the DS3 signal QRSS Quasi Random Signal Source A modified 2 20 1 pseudorandom test signal that has artificial constraints to limit the maximum number of zeros in the bit...

Страница 10: ...nd checksums for the NIU3 PM Figure 7 Adtran NIU3 Main Menu Screen Figure 8 NIU3 Unit Information Screen CIRCUIT ID xxxxxxx 03 01 04 13 04 03 Adtran NIU3 Main Menu 1 NIU3 Unit Information 2 Provisioni...

Страница 11: ...equipment whose receiver is sensitive to signal levels in the upper range of T3 specifications In this case the Tx Level to Customer option may be set to Low to reduce the customer transmit signal le...

Страница 12: ...tatus Screen NETWORK T3 RECEIVER DATA CUSTOMER LIVE DS3 SIGNAL LOS ______ C BIT FRAMING UNFR NIU3 3 6 dBdsx LEVEL 2 9 NET CUST 15M 24H 30D 15M 24H 30D AIS LOS 000 00000 0000000 ES L 000 00000 0000000...

Страница 13: ...ors From the Troubleshooting Screen it is possible to make the following selections Receive Guidance in problem resolution Clear the Performance Monitoring information Clear the Alarm History View Per...

Страница 14: ...ly the following warnings will display immediately upon occurrence on the Network and Customer interface Receive Level Low or High Receive Frequency Lock Error The Receive Frequency Lock Error provide...

Страница 15: ...n the next screen Figure 13 shows an active network loopback Figure 13 Loopback and Test Commands Screen NTWK LBK Active CIRCUIT ID xxxxxxx 03 01 04 13 04 03 Press ESC to return to previous menu Loopb...

Страница 16: ...the customer and it can be set to C BIT M13 or UNFR unframed The Timing Source for Pattern option selects whether the received network DS3 signal NTWK or the NIU3 PM local reference clock LOCAL will b...

Страница 17: ...30 000 000 000 00000 6 30 Days Data 01 01 12 15 000 000 000 00000 7 Line Data 01 01 12 00 000 000 000 00000 8 Path Data 1 01 01 11 45 000 000 000 00000 9 Path Data 2 01 01 11 30 000 000 000 00000 10...

Страница 18: ...MSEC 00000 00000 00000 00000 0000000 3 15 Min Data 03 01 00000 00000 00000 0000000 4 60 Min Data 02 29 00000 00000 00000 0000000 5 24 Hr Data 02 28 00000 00000 00000 0000000 6 30 Day Data 02 27 00000...

Страница 19: ...ear end only The Path Related thresholds set the thresholds for the near and far path parameters for both network and customer All thresholds can be disabled or reset to factory default Figure 19 Perf...

Страница 20: ...SEF 1 or AIS 1 UAS P Unavailable Seconds 10 cont SES Ps CV P Code Violation Count Parity Error Count NOTE Reverse video indicates invalid data due to a terminal restart or power cycle a data register...

Страница 21: ...og choose R for Reset This reset must be confirmed by choosing Y on the next screen Possible events include the following Status changes Provisioning commands Loopback commands remote and manual Power...

Страница 22: ...or NIU3 local to the NIU3 PM To clear the alarm log choose R This reset must be confirmed by choosing Y on the next screen Possible alarms include the following Power events Alarm log reset FEAC alar...

Страница 23: ...NIU3 PM date and time Once date and time are configured the date and time performance registers update accordingly Figure 25 Set Circuit ID and Scratch Pad Figure 26 Set System Date and Time CIRCUIT I...

Страница 24: ...UPDATE 03 01 04 02 04 03 Press ESC to return to previous menu TERMINAL MODES MENU MANUAL UPDATE MODE You can print or log screens No text is highlighted Ctrl R TO UPDATE appears at the top of each scr...

Страница 25: ...d press ENTER 5 From the Software Download menu to begin YModem download select option 1 press ENTER 6 A screen appears stating that the NIU3 PM is waiting for download and the character C appears acr...

Страница 26: ...ork direction The remaining codes send the associated test pattern in both network and customer directions simultaneously To deactivate a loopback or test pattern send 1110110 and the NIU will respond...

Страница 27: ...ector Ntwk LOS Indication Ntwk AIS Indication Ntwk C Bit M13 Indication Regen Cust Out Cust In Network Loopback Regen Ntwk Out Ntwk In Customer Monitor Network To Network Monitor Customer To RCV Frami...

Страница 28: ...m the following steps 1 Insert a jumper strap on the posts immediately adjacent to the suspect relay This provides a signal path bypassing the relay 2 Using an appropriately sized IC extractor tool li...

Страница 29: ...es T400 density NIU3 PM circuit board 8 ounces Standalone housing 2 pounds 3 slot shelf 4 pounds 12 slot shelf 12 pounds Environmental Operating Temperature Storage Temperature Relative Humidity 40 C...

Страница 30: ...30 Issue 5 February 2011 61213075L2 5E...

Отзывы: