CS2-CT-2010-10-03
C2-17
-1/8
CS2-CT MULTIFUNCTION Counter
(Pulse input)
DESCRIPTION
The CS2-CT provides high speed and multifunction, counting,
control and communication (Modbus RTU mode) of Pulse from flow
meter or encoder, proximity switch, photo switch for length control.
There are 3 external control input (DI) in standard and the optional 4
Relay, 1 Analogue, 1 Pulse and RS485 port available. They are also
support N, R, C mode for totalizer control.
FEATURE
●
Measuring Pulse 0.01Hz~20KHz(optional: over 20KHz~50KHz); Contact / NPN / PNP / Voltage Pulse can be
switch on rear of meter
●
4 banks pre-set for all relay functions relative 4 difference application, and selectable by 3 External Control
Inputs(E.C.I.) or front key in optional
●
4 relay can be individual programmed for N/R/C mode and energized time.
●
3 external control input can be individual programmed for Reset, Gat
●
Analogue Output and RS485(Modbus RTU mode) available in option
●
Comply to CE standard & RoHS
ORDERING INFORMATION
CS2
−
CT
−
Input Range
−
Relay
Output
−
Analogue
Output
−
RS 485 Port
−
Pulse
Output
−
AUX.
POWER
CODE INPUT RANGE CODE REALY O/P CODE ANALOG O/P CODE RS 485 PORT CODE PULSE O/P
CODE AUX. POWER
C
Mech. contact
N
None
N
None
N
None
N
None
A
AC 115/230 V
N
NPN
R2
2 Relay
8
RS 485
C
Open Collect
P
PNP
R3
3 Relay
V
0(1) ~ 5 V
0 ~ 10 V
R
Relay Contact
V
Voltage pulse
R4
4 Relay
ADH
AC 85~264V
DC 100~300V
05
5V pulse
I
0 ~ 10 mA
0(4)~20 mA
ADL
AC/DC 20~56V
12
12V pulse
24
24V pulse
O xx
Specify
* If the pulse output is
to be selected, the
meter can be
selected 3 relay
maximum.
Energized mode:
N / R / C Mode
TECHNICAL SPECIFICATION
Period of Relay on:
0:00.0~9(Minutes):59.9(Second)
Input
DO function: Energized by RS485 command of master.
Input Frequency
Input Mode
Input Level
Banks pre-set:
0.01Hz ~ 50 Hz
Mech. Contact
NPN
4 banks pre-set for all relay functions to relative 4
difference control condition, and selectable by 3 External
Control Inputs(E.C.I.) or front key
PNP
High Level: 8~12V; Low Level: 0.0~4.0 V
(with excitation supply 12Vdc)
Voltage Pulse
High Level: over 2/3 of input level
Low Level: under 1/3 of input level
External Control Inputs(ECI)
0.01Hz ~ 50 Hz
0.01Hz ~ 100KHz
0.01Hz ~ 140KHz
(optional)
Pick Up Sensor
Specified by order
Input mode:
3 ECI points, Contact or open collect input, Level trigger
Functions:
Gate / Reset / Offset / Bank selection(option) programmable
Input Mode(NPN, PNP, Contact) & Level(5Vp, 12Vp, 24Vp) changeable
by dip switch of rear terminal block.
Debouncing time:
Settable range 5 ~255 x (8m seconds)
Input range:
0.01Hz~20kHz (~50kHz in option)
Sampling time:
0.05 m-second~100 seconds (0.02 m-second in option)
Analogue output(option)
Response time:
≤
100 m-sec.(when the AvG = “1”) in standard
Accuracy:
≤
±
0.1% of F.S.; 16 bits DA converter
Ripple:
≤
±
0.1% of F.S.
Response time:
≤
100 m-sec. (10~90% of input)
Display & Functions
Isolation:
AC 2.0 KV between input and output
LED:
Numeric:
5 digits, 0.8”(20.0mm)H red high-brightness LED
Output range:
Specify either Voltage or Current output in ordering
Relay output indication:
4 square red LED
Voltage:
0~5V / 0~10V / 1~5V programmable
RS 485 communication:
1 square orange LED
Current:
0~10mA / 0~20mA / 4~20mA programmable
E.C.I. function indication:
3 square green LED
Output capability:
Voltage: 0~10V:
≥
1000
Ω
;
Display range:
0.0000~99999
with auto moving of decimal point
Current: 4(0)~20mA:
≤
600
Ω
max
Factor Setting:
Functions:
aOhs
(output range high): Settable range: -19999~99999
Settable Range: -19999~+99999 with decimal point
settable 0 / 0.0 / 0.00 / 0.000 / 0.0000
aOls
(output range Low): Settable range: -19999~99999
Decimal Point:
Settable: 0 / 0.0 / 0.00 / 0.000 / 0.0000
aOlmt
(output High Limit): 0.00~110.00% of output High
Over Flow indication:
Overflow
ovfl
/ Re-cycle
rcycl
counting programmable
Digital fine adjust:
aOzro
:
Settable range: -38011~+27524
Compensation setting:
Option:
Settable range: -19999~+99999
aOspn
:
Settable range: -38011~+27524
Digital adjustment:
Option:
cTspn
:
Settable range: -19999~99999
Control Functions(option)
Set-points:
Four set-points
Control relay:
Four relays
Relay 2 & Relay 3: Dual FORM-C, 5A/230Vac, 10A/115V
Relay 1 & Relay 4: Dual FORM-A, 1A/230Vac, 3A/115V
CSM-321S
CS2-
V
A
CSM-321S CSM-
CSM-
CS2-CT
CSM-321S CSM-
CSM-
CSM-321S
CSM-
CSM-321S
OPTION
OPTION
OPTION
OPTION 4
Input mode and level
can be changed by
dip switches on rear
of meter