CS2-CT-2010-10-03

 

C2-17

-5/8

 

 

 

 

 

 

„

 

OPTIONAL FUNCTION   

 
 
 

Customize function with quantities is welcome. Please contact with our 

sales for detail. The appendix code of optional function will be add 
behind the code of auxiliary power as like as xxx-A-3BK.

 

 

„

 

BANK FUNCTION(Suffix-3BK)

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

The function is for CS2 to control difference process with a same 
meter. 

 

 

For example; a pressure testing equipment; it has to measure 
multi-range with difference pressure transducers. The meter can be 
pre-set 4 groups parameter to show difference scale and relay 
energized in difference set-points. The operator just selects the 
bank number (bank1) to meet the process (product A). To make 
easier operating and to avoid mistake in process. 

 

The bank function is available in CS2-CT (optional) too. It’s useful to 
control as like as filling machine, Air flow measurement with 
difference sensor. 

 

4 banks pre-set for all relay functions relative 4 difference scaling, 
decimal point, and select by 3 External Control Inputs(E.C.I.) or 
front key. 

 

 

 

 

 

 

Example: 

Product A

: Flowmeter: 1.0000L/sec;    Set-Point: 2.0000L 

Output: RS485 

Product B

: Flowmeter: 5.000L/sec;   Set-Point: 6.000L 

Output: RS485 

Setting: 

BANK1: 

[

   dp

]

)0000

     

[

ry!md

]

totLr

   

[

ry!sp

]

@0000

   

[

ry!ot

]

 )0)5

0(M).00.5(S) 

BANK2: 

[

   dp

]

 )000

     

[

ry!md

]

totLr

   

[

ry!sp

]

 ^000

             

[

ry!ot

]

: 0

 )0!0

 (M).01.0(S) 

ECI.1

: Bank.1    

ECI.2

: Bank.2;     

connect to a selector (or DO of PLC) to ECI1 and ECI2 

X

 

The order want to produce 

Product A,

 to switch selector to A(Label 

A

 on 

panel), and then ECI.1 close, the square green LED bright. The meter will 
work base on the setting of bank1 and relay1 output on 2.0000. 

X

 

The second order want to produce 

Product B,

 to switch selector to 

B(Label 

B

 on panel), and then ECI.2 close, the square green LED 

bright. The meter will work base on the setting of bank2 and relay1 
output on 6.000. 

 

Only 1 Bank can be selected. The priority is Bank1 > Bank2 > Bank3, if it 
is double selection.

 

 

 

„

 

ERROR 

MESSAGE

 

BEFORE POWER ON, PLEASE CHECK THE SPECIFICATION AND CONNECTION AGAIN. 
SELF-DIAGNOSIS AND ERROR CODE

DISPLAY 

DESCRIPTION 

REMARK 

 ovfl

 

 

Display is positive-overflow (Signal is over display range)

 

(Please check the input signal) 

-ovfl

 

 

Display is negative-overflow (Signal is under display range) 

(Please check the input signal) 

 ovfl

 

 

ADC is positive-overflow (Signal is higher than input 

range 

high 20%

(Please check the input signal) 

-ovfl

 

 

ADC is negative-overflow (Signal is lower than input 

range low 

-20%

(Please check the input signal) 

  eep

 

 

 

 fail

 

EEPROM occurs error 

(Please send back to manufactory for repaired)

aiCng

 

 

 

   pv

 

Calibrating Input Signal do not process 

(Please process Calibrating Input Signal) 

  aic

 

 

 

 fail

 

Calibrating Input Signal error 

(Please check Calibrating Input Signal) 

aoCng

 

 

 

   pv

 

Calibrating Output Signal do not process 

(Please process Calibrating Output Signal) 

  aoc

 

 

 

 fail

 

Calibrating Output Signal error 

(Please check Calibrating Output Signal) 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

CSM-321S 

CS2-

V

CSM-321S CSM-

CSM-

CS

2-

CT

 

CSM-321S CSM-

CSM-

CSM-321S 

CSM-

CSM-321S 

Содержание CS2-CT

Страница 1: ...e High Level over 2 3 of input level Low Level under 1 3 of input level External Control Inputs ECI 0 01Hz 50 Hz 0 01Hz 100KHz 0 01Hz 140KHz optional Pick Up Sensor Specified by order Input mode 3 ECI...

Страница 2: ...elay 4 a c Analogue output A B RS 485 port ECI1 ECI3 COM ECI2 External Control Input 4 5 3 6 7 8 9 10 11 12 14 15 13 Terminal blocks 10A 300Vac M2 6 M2 6 1 3 2 0mm2 16 22AWG AC 86 265V DC 100 300V DC...

Страница 3: ...ON OFF status of switch from CS2 series with RS485 function If the ry_ md had been set do the relay will be energized by RS485 command directly but no longer to compare with set point Control Function...

Страница 4: ...log Output 0 10V 0 4 20mA 3 External Control Input Functions Relative PV PV Hold Reset Max or Mini Hold DI Reset for Relay Energized Hold Application Thermal Switch Circuit Breaker Push Button Display...

Страница 5: ...he order want to produce Product A to switch selector to A Label A on panel and then ECI 1 close the square green LED bright The meter will work base on the setting of bank1 and relay1 output on 2 000...

Страница 6: ...ack to previous function index Down key Decrease number Go to next function index Shift key Shift the setting position Go back to this function index and abort the setting Enter Fun key Setting Confir...

Страница 7: ...2 0 aOls aOls Analogue Low Output versus Low Scale 19999 99999 A 3 0 ttLdp ttLdp Decimal point of totalizer 0 0 0000 B 3 totLn ry md ry md Relay 2 energized mode off do totLn totLr totLc C 3 none ecI3...

Страница 8: ...Flock Function Level Lock none user eng all rs485 group ENT RS485 GROUP E 1 1 adres adres Device number of the meter 1 255 E 2 9600 baud baud Baud rate 1200 2400 4800 9600 19200 38400 E 3 NstB2 prity...

Отзывы: