background image

!

EIGHT SELECTABLE COUNT MODES

!

BATCH COUNTING INDICATION

!

NON-VOLATILE MEMORY

!

SIGNAL INPUT SWITCH SELECTABLE FOR HI or LO

FREQUENCY OPERATION

!

ACCEPTS INPUT COUNT RATES UP TO 12 KHZ

!

SIMPLIFIED FRONT PANEL PROGRAMMING

!

ON LINE SELF-TEST (Including Relay Test)

!

PROGRAMMABLE TIMED OUTPUT

!

FRONT PANEL RESET ENABLE/DISABLE

!

REMOTE RESET CAPABILITY

!

LEADING ZERO BLANKING

!

NEMA 4/IP65 SEALED METAL FRONT BEZEL

DESCRIPTION

The CUB Controller Counter is a versatile compact presettable counter.

Batch counting indication is a feature of the Model CUBCB.  All data set-ups
are stored in a non-volatile internal memory. When power is removed, count
and batch totals are saved.

The CUB Controller Counter features eight different DIP switch selectable

counting modes. The timed output is programmed via the front panel buttons.

The unit also has a built-in self-test which checks the display driver and

microprocessor hardware. The self-test can be run at any time without losing
counts.

Power and Output connections are made at a terminal block at the rear of the

unit. The Input connections are made via a five pin polarized connector on the
bottom of the unit. This connector includes the count input, remote reset, front
panel reset enable, and signal common.

The metal front bezel meets NEMA 4/IP65 specifications for wash down

and/or dusty environments when properly installed.

SPECIFICATIONS

1. 

DISPLAY:

6-Digit LCD, 0.2" (5.1 mm.) high digits.

2. 

POWER REQUIREMENTS:

A.C. Power Versions

: 115 VAC ±10%, 50/60 Hz, 0.5 VA.

230 VAC ±10%, 50/60 Hz, 0.5 VA.
10 to 28 VAC ±10%, 50/60 Hz, 2.5 VA.

D.C. Power Version

:  10 to 28 VDC, 1 W.

3. 

OUTPUT RELAY:

Type

: Form-A.

Max. Power

: 50 VA

Max. Voltage

: 250 VAC/DC

Max. Current

: 0.75 Amps

Operate Time

: 0.5 msec. nominal

Release Time

: 0.3 msec. nominal

Note: Relay output can switch an RLC DPDT relay P/N RLY30000 (115

VAC-10 Amp).

Programmable Timed Output

: 0.01 sec. to 99.99 sec. ±1% +10 msec. max.

4. 

SIGNAL INPUT:

Connect to the white wire (CNT./TIM.) and black wire

(Common) of the five position connector. The unit counts on the negative
edge of the input signal.

High Frequency Operation

: DIP switch position 1 OFF. 12 KHz, 50% duty

cycle.

Low Frequency Operation

: DIP switch position 1 ON. Limits count speed

to 50 Hz.

Note: These units will operate with RLC VCM modules E through H.

Threshold Levels

: V

IH

= 3.3 V, V

IL

= 1.0 V

Current Sourcing

: 30 VDC max, use external 560-1000 

Ω 

pull-down

resistor to comm to count.

Current Sinking

: Internal 5 K

pull-up to +5 VDC, I

MAX

= 1.2 mA.

5. 

REMOTE RESET:

Blue wire must be inserted into the five position

connector.

Threshold levels

: V

IH

= 2.5 V, V

IL

= 0.8 V, V

MAX

= 5 V. Response time =

10 msec max.

Current Sinking

: I

MAX

= 750 µA.

6. 

MEMORY:

Non-volatile E

2

PROM retains all programmed information

when power is removed or interrupted.

Power Cycles (ON/OFF)

: 100,000 min.

MODEL CUBC - SINGLE PRESET COUNTER AND

CUBCB - SINGLE PRESET COUNTER W/BATCH INDICATION

DIMENSIONS  “In inches [mm]”

Note: Recommended minimum clearance (behind the panel) for mounting clip installation

is 2.77" (70.4)H x 2.77" (70.4)W.

PANEL CUT-OUT

Bulletin No.  CUBC/CB-F
Drawing No.  LP0277
Revised  3/01

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Отзывы: