70
Table 25: Examples of EtherNet/IP-Style Bulk Access via File N50
File/Section
Number
Offset/Element Address
Format
Start Target Parameter of
Configuration Array
Max Number of
Accessible Elements
N50
0
N50:0
1st
32
N50
:
:
:
:
N50
15
N50:15
16th
16
N50
:
:
:
:
N50
31
N50:31
32nd
1
The application PLC program uses a MSG instruction that is configured with a “Data Table Address”
from which to start the access and a “Size in Elements” which determines the number of items to access
(read or write). The “Data Table Address” is constructed by selecting a “File/Section Number” and an
“Offset/Element” according to Equation 7. For example, a “File/Section Number” of N10 and
“Offset/Element” of 3 = N10:3, which corresponds to register 3 (the inverter’s run command, parameter
00.02).