94
Figure 82: Updated GSDML Device Tree
9.5.7.2
Add the device to the configuration
Select the device in the
Hardware catalog
and drag the device onto the PROFINET IO system
configuration as shown in Figure 83.
Figure 83: Add Device to Configuration
9.5.7.3
Select the IO controller
On the device, click “Not assigned” and select the appropriate PLC PROFINET interface as shown in
Figure 85. This will assign the device to the PROFINET IO system as shown in Figure 84.
9.5.7.4
Assign IO module
Click on the device and then click on the
Device view
tab. In the
Hardware catalog
, expand
Module
and add a module “IN: XX WORDS, OUT: YY WORDS” into
Slot
1. The module will determine the input
and output sizes. In this example, the module “IN: 02 WORDS, OUT: 02 WORDS” is selected. Select a
module with the appropriate input and output sizes for your specific application. Refer to Figure 86.
Figure 84: PROFINET IO System
Figure 85: Select IO Controller