7 −  Vent termination must be a minimum of 6 feet (1.83 

m)  from  an  inside  corner  formed  by  two  exterior 

walls. If possible, leave a 10−foot clearance.

 

 

8 −  Vent  termination  must  be  a  minimum  of  10  feet 

(3m)  from  any  forced  air  inlet  (includes  fresh  air 

inlet for other appliances, such as a dryer).

 

 

9 −  For upward sloped vent, a condensate tee and drain 

must be installed within the first 5 feet (2m) from the 

duct  heater  to  protect  the  appliance.    If  the  unit  is 

shut down for an extended period of time and will be 

exposed  to  sub-freezing  temperatures,  the 

condensate may freeze.

 

 

10 − For  upward  sloped  vent,  see  figure  3,  condensate 

tee and drain must be installed within the first 5 feet

 

 

(1.53 m) from the duct heater to protect the 

appliance.

 

 

11 − Flexible  loop  trap  in  condensate  line  (if  used) 

must  be  filled  with  water  to  prevent  combustion 

products from entering structure.

 

12 − Select  a  wall  termination  point  that  will  maintain 

1/4"  rise  per  foot  slope  of  horizontal  run  of  vent 

pipe. In areas where authorities having jurisdiction 

permit,  a  downward  slope  of  maximum  1/4"  per 

foot is also acceptable. Condensate drainage can 

be  collected  in  a  tee  pipe  section  (figure  4)  with 

drain  loop  similar  to  one  used  for  upward  slope 

vent,  or  allowed  to  drip  through  the  vent 

termination, if permitted by authorities (Fig 5).

 

 

13  For  horizontal  venting,  the  vent  pipe  must  be 

supported with hangers no more than 3 feet (1m) 

apart to prevent movement after installation.

 

 

14 − All  horizontal  vent  applications  which  use  Category 

III  vent  pipe  must  terminate  with  an  approved 

Category III tee. Opening end must face downward.

 

 

15 − When  termination  is  routed  through  an  exterior 

combustible  wall  the  vent  must  be  supported 

using  a  listed  clearance  thimble.  Inside  edge  of 

vent termination tee or elbow must be at least 12" 

(305mm) from outside wall.

 

 
 
 

 

 

 

 

 

COMBUSTION  AIR  INDUCER  CAN 

BE  ROTATED  ON  UNITS  HED−75, 

−100, −125 and −150 ONLY.

 

 
 

NOTE − FOR HED−200, 

−230, −250 and 300 −− DO 

NOT ROTATE THE 

COMBUSTION AIR 

INDUCER; USE 90° ELBOW.

 

 
 

NOTE − Minimum horizontal length 

equals 5 feet (1.53 m).This does 

not include termination tee. Refer to 

table 3 for maximum length and 

number of elbows.

 

 

 

HORIZONTAL VENTING

 

Venting may be single−wall (26

 

 

UPWARD SLOPE

 

GSG) galvanized or equivalent

 

 

stainless steel vent pipe sealed per

 

 

 

 

 

these instructions, OR listed special

 

 

 

vent for Category III appliances.

 

 

 

 

 

SLOPE = 1/4 IN. PER FOOT RUN

 

 

COMBUSTION

 

CATEGORY III

 

MAXIMUM.

 

 

AIR INDUCER

 

ADAPTER

 

12 INCHES MIN.

 

 

(Make airtight using

 

 

 

 

 

high−temperature

 

(30.5 CM)

 

 

 

sealant provided in kit)

 

 

 

 

 

VENT TERMINATION

 

 

 

 

TEE

 

 

 

LISTED WALL

 

 

 

 

THIMBLE THROUGH

 

12" (30.5CM)

 

 

 

COMBUSTIBLE WALL

 

MINIMUM ABOVE

 

 

 

 

HIGHEST

 

 

 

 

SNOWFALL

 

 

 

DRAIN LOOP WITH

 

 

 

 

WATER TRAP TO

 

 

 

 

CONDENSATE TRAP

 

 

 

 

(Provided by installer)

 

GROUND LEVEL

 

 

 

FIGURE 4

 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

8

Содержание HED Series

Страница 1: ...mplate 17 Warranty 18 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exact ly could result in serious injury death or property damage Be sure to read and understand the installation operation and service instructions in this manual Improper installation adjustment alter ation service or maintenance can cause serious injury death or...

Страница 2: ... in 31 5 16 32 3 16 41 1 8 3 11 16 40 17 1 2 3 1 4 25 39 1 8 15 3 8 35 1 16 9 HED 250 A S mm 795 817 1045 97 1016 445 83 635 994 391 891 229 HED 300 A S A Heat Exchanger Aluminum Steel S Heat Exchanger Stainless Steel Shipping The heater is completely assembled and is shipped with installation and operating instructions warranty certificate and flue transition Check the unit for shipping damage Th...

Страница 3: ...e area clearance from the heater to combustible materials must be such that the combustible material must not attain a temperature above 160 F 71 C during continuous operation of the unit WARNING These units are CSA international design certified These duct heaters are certified for clearances to combustible material as listed in table 1 and on unit rating plate Accessibility and service clearance...

Страница 4: ...onnection and not less than 2 equivalent diameters in length See figure 1 SINGLE BLOWER APPLICATION Top View 155 TRANSITION HED UNIT BLOWER AIR FLOW DUCT LENGTH L The formula for computing duct length L is 4WH W WidthH Height Inlet W H Duct length L is computed as shown by the formula and rounded to the nearest whole number MODEL INLET DUCT in mm DUCT NO WIDTH HEIGHT LENGTH L HED 75 15 13 3 8 29 3...

Страница 5: ... rotate the combustion air inducer on HED models 200 250 and 300 Rotate the combustion air inducer assembly as follows 1 Remove the heater from the carton Decide the best duct heater orientation The vent can be installed in one of three discharge positions up left or right 2 If the inducer is to be rotated follow the instructions in this section otherwise refer to instructions under Venting sectio...

Страница 6: ...l HED duct heaters are listed as Category 1 appliances for vertical vent installations 1 All HED duct heaters are to be used with NFPA or ANSI approved chimneys or U L listed type B 1 gas vents where applicable as well as the modifications and limitations listed in figure 2 Seal single wall vent material according to General Recommendations and Requirements section 2 Keep the vent connector runs a...

Страница 7: ...ct heater If the HED duct heater is to be horizontally vented a positive pressure may be created in the vent The duct heater when installed with horizontal venting will perform as a category III appliance 1 Special vent materials approved for use with Category III appliances may be used with these units Refer to table 7 for venting components 2 If possible do not terminate the horizontal vent thro...

Страница 8: ...he vent termination if permitted by authorities Fig 5 13 For horizontal venting the vent pipe must be supported with hangers no more than 3 feet 1m apart to prevent movement after installation 14 All horizontal vent applications which use Category III vent pipe must terminate with an approved Category III tee Opening end must face downward 15 When termination is routed through an exterior combusti...

Страница 9: ...ructions OR listed special vent for Category III appliances SLOPE 1 4 IN PER FOOT RUN MAXIMUM NOTE Minimum horizontal length equals 5 feet 1 53 m This does not include termination tee Refer to table 6 for maximum length and number of elbows 12 INCHES 30 5 cm MINIMUM DOUBLE MALE VENT TERMINATION ADAPTER TEE Cat III kits only FIGURE 6 TABLE 5 Category III Horizontal Venting Components Required for H...

Страница 10: ...fused disconnect switch with the fuse sized according to blower motor size Connect wiring through knockout on the junction box located on the side of the duct heater Refer to heater wiring diagram for connection information Use 18 gauge wire or larger for thermostat connections NOTE Electrically ground unit in accordance with local codes or in the absence of local codes in accordance with the curr...

Страница 11: ...hese devices should be properly labeled by the installer GAS SUPPLY TO UNIT HEATER MANUAL MAIN SHUT OFF DISCONNECT GAS VALVE WILL NOT HOLD NORMAL TEST VALVE WHEN TEST PRESSURES OF 1 2 psig PRESSURES OF 1 2 psig 3 45kPa 3 45kPa OR HIGHER OR HIGHER WILL BE USED CAP UNIT HEATER FIGURE 8 Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not u...

Страница 12: ...ttempt to light the burners manually 5 Honeywell VR8205 series turn manual knob on gas valve clockwise to OFF Do not force For White Rodgers 36 series gas valve move lever to OFF 6 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not smell gas go to next step 7 Honeywell VR8...

Страница 13: ...ximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the ACC terminals approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed Five seconds after the demand is satisfied the combustion air inducer is shut off 9 The ignition control will de energize the ACC terminals approximat...

Страница 14: ...e switch is factory set and no field adjustment is necessary Service LUBRICATION Combustion air inducer motor bearings are pre lubricated and sealed No further lubrication is necessary BURNERS 1 Periodically examine burner flames for proper appearance during the heating season 2 Before each heating season examine the burners for any deposits or blockage that may have occurred 3 Clean burners as fo...

Страница 15: ...nit unit operating 3 Check amperage draw FLUE AND CHIMNEY Check all vent and vent connector joints for tightness Ensure that connections are sealed and that there are no blockages FAILURE TO OPERATE If unit fails to operate check the following 1 Is thermostat calling for heat 2 Is main disconnect closed 3 Is there a breaker tripped or a fuse blown 4 Is gas turned on at meter 5 Is manual shutoff va...

Страница 16: ...l No Serial No Service Technician Electrical Connections Tight Air Shutters Properly Adjusted If Installed Supply Voltage Flue Connections Tight Blower Motor Lubrication O K Gas Piping Connections Tight Leak Tested THERMOSTAT Furnace Btu Input Calibrated Heat Anticipator Properly Set Line Pressure Manifold Pressure w c Level 16 ...

Страница 17: ...TEMPLATE Location of Combustion Air Inducer Mounting Holes for Rotated Inducer EXISTING HOLE EXISTING HOLE EXISTING HOLE 17 ...

Страница 18: ... credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for HED series heat exchangers For information on this product s warranty including accessing complete warranty terms registering for an extended warranty or obtaining instructions on filing a warranty claim please go to www ADPwarranty com In such states or ...

Страница 19: ...19 ...

Страница 20: ......

Отзывы: