Adp HED Series Скачать руководство пользователя страница 4

As with any mechanical equipment, personal injury 

can  result  from  contact  with  sharp  sheet  metal 

edges. Be careful when you handle this equipment.

 

CAUTION

 

 

3 −  Heaters  should  be  located  so  that  they  are 

protected  from  damage  from  aircraft  or  other 

appliances needed for servicing of aircraft. Refer 

to requirements of the enforcing authorities.

 

 

In  a  confined  area,  the  heater  must  be  installed  in 

accordance  with  the  current  edition  of  CSA-B149 

installation  compliance  codes.  Be  sure  to  check  with 

local codes and ordinances for additional requirements.

 

 

Additional Requirements

 

 

The  Commonwealth  of  Massachusetts  stipulates  the 

following additional requirements:

 

 

1 − Gas furnaces shall be installed by a licensed 

plumber or gas fitter only.

 

 

2 −  The gas cock must be  T handle" type.

 

 

Duct Heater Installation

 

 

 

Connect  the  return  air  and  supply  air  ducts  to  unit.  The 

unit must be installed on the positive pressure side of the 

circulating air blower. The CFM through the unit must be 

adjusted within the range listed on the unit rating plate.

 

The air flow pattern must be reasonable and even.

 

 

Failure to comply with these adjustments may void 

the  warranty.

  The  connecting  duct  to  the  unit  shall 

have removable access panels on both upstream and 

downstream sides of the duct heater. These openings 

shall  be  accessible  when  the  furnace  is  installed  in 

service  and  shall  be  of  such  size  that  smoke  or 

reflected  light  may  be  observed  inside  the  casing  to 

indicate  the  presence  of  leaks  in  the  heat  exchanger. 

The cover for the openings shall be attached in such a 

manner as to prevent leaks.

 

 

A  duct  furnace  shall  be  installed  with  an  inlet  duct 

which  will  provide  air  distribution  equivalent  to  a 

straight  run  of  duct  having  the  same  cross-sectional 

area  as  the  inlet  connection  and  not  less  than  2 

equivalent diameters in length. See figure 1.

 

 

SINGLE BLOWER APPLICATION

 

(Top View)

 

 

                                              155

 

 

TRANSITION

 

HED UNIT

 

BLOWER

 

AIR FLOW

 

 

 

DUCT

 

   

LENGTH  “L"

 

 

 

The formula for computing duct length L" is:

 

4WH

 

W = WidthH = Height (Inlet)

 

 

W + H

 

 

Duct length L" is computed as shown by the formula, and 

rounded to the nearest whole number.

 

 

MODEL

 

INLET DUCT −− in. (mm)

 

DUCT

 

 

NO.

 

WIDTH

 

HEIGHT

 

LENGTH  “L"

 

 

HED−75

 

15

 

13−3/8

 

29

 

 

(381)

 

(340)

 

(737)

 

 

 

 

HED−100, −125

 

15−5/8

 

15−3/8

 

31

 

 

(397)

 

(391)

 

(788)

 

 

 

 

HED−150

 

17−1/8

 

15−3/8

 

33

 

 

(435)

 

(391)

 

(839)

 

 

 

 

HED−200,−25O,

 

35−1/16

 

15−3/8

 

43

 

 

−300

 

(891)

 

(391)

 

(1093)

 

 

 

FIGURE 1

 

 

NOTE

  −  The  appliance  may  be  installed  downstream 

from  refrigerated  units  supplying  air  below  the  dew 

point  of the ambient air surrounding the  appliance.   A 

¼” barbed connection under the burner box is provided 

for condensate drainage.

 

 

The duct connection from the blower to the unit must be 

a smooth transition. Any side of the transition shall not 

taper more than 15°. Where elbows or turns are used, 

proper  air  distribution  can  be  obtained  by  the  use  of 

properly designed air turns.

 

 

NOTE

 − Do not install heater in explosive or flammable 

atmosphere, laden with grain dust, sawdust, or similar 

airborn  materials.  Do  not  install  heater  where  direct 

contact with water may occur.

 

 

Install  the  unit  in  the  desired  location  as  governed  by 

clearances,  vent  connection,  air  direction,  gas  supply, 

electrical supply and service accessibility.

 

 

 

 

Improper installation, adjustment, alteration, service 

or  maintenance  can  cause  property  damage, 

personal  injury  or  loss  of  life.  Installation  and 

service  must  be  performed  by  a  licensed 

professional installer (or equivalent), service agency 

or the gas supplier.

 

 

IMPORTANT

 

 

In these conditions, condensate will form in the duct 

heater.  A  condensate  drain  connection  is  provided 

on the duct heater for condensate removal. Installer 

must  make  adequate  provisions  to  route 

condensate  from  this  drain  connection.  The 

condensate  drain  should  be  checked  periodically 

and cleaned as required.

 

 

CAUTION

 

 

4

Содержание HED Series

Страница 1: ...mplate 17 Warranty 18 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exact ly could result in serious injury death or property damage Be sure to read and understand the installation operation and service instructions in this manual Improper installation adjustment alter ation service or maintenance can cause serious injury death or...

Страница 2: ... in 31 5 16 32 3 16 41 1 8 3 11 16 40 17 1 2 3 1 4 25 39 1 8 15 3 8 35 1 16 9 HED 250 A S mm 795 817 1045 97 1016 445 83 635 994 391 891 229 HED 300 A S A Heat Exchanger Aluminum Steel S Heat Exchanger Stainless Steel Shipping The heater is completely assembled and is shipped with installation and operating instructions warranty certificate and flue transition Check the unit for shipping damage Th...

Страница 3: ...e area clearance from the heater to combustible materials must be such that the combustible material must not attain a temperature above 160 F 71 C during continuous operation of the unit WARNING These units are CSA international design certified These duct heaters are certified for clearances to combustible material as listed in table 1 and on unit rating plate Accessibility and service clearance...

Страница 4: ...onnection and not less than 2 equivalent diameters in length See figure 1 SINGLE BLOWER APPLICATION Top View 155 TRANSITION HED UNIT BLOWER AIR FLOW DUCT LENGTH L The formula for computing duct length L is 4WH W WidthH Height Inlet W H Duct length L is computed as shown by the formula and rounded to the nearest whole number MODEL INLET DUCT in mm DUCT NO WIDTH HEIGHT LENGTH L HED 75 15 13 3 8 29 3...

Страница 5: ... rotate the combustion air inducer on HED models 200 250 and 300 Rotate the combustion air inducer assembly as follows 1 Remove the heater from the carton Decide the best duct heater orientation The vent can be installed in one of three discharge positions up left or right 2 If the inducer is to be rotated follow the instructions in this section otherwise refer to instructions under Venting sectio...

Страница 6: ...l HED duct heaters are listed as Category 1 appliances for vertical vent installations 1 All HED duct heaters are to be used with NFPA or ANSI approved chimneys or U L listed type B 1 gas vents where applicable as well as the modifications and limitations listed in figure 2 Seal single wall vent material according to General Recommendations and Requirements section 2 Keep the vent connector runs a...

Страница 7: ...ct heater If the HED duct heater is to be horizontally vented a positive pressure may be created in the vent The duct heater when installed with horizontal venting will perform as a category III appliance 1 Special vent materials approved for use with Category III appliances may be used with these units Refer to table 7 for venting components 2 If possible do not terminate the horizontal vent thro...

Страница 8: ...he vent termination if permitted by authorities Fig 5 13 For horizontal venting the vent pipe must be supported with hangers no more than 3 feet 1m apart to prevent movement after installation 14 All horizontal vent applications which use Category III vent pipe must terminate with an approved Category III tee Opening end must face downward 15 When termination is routed through an exterior combusti...

Страница 9: ...ructions OR listed special vent for Category III appliances SLOPE 1 4 IN PER FOOT RUN MAXIMUM NOTE Minimum horizontal length equals 5 feet 1 53 m This does not include termination tee Refer to table 6 for maximum length and number of elbows 12 INCHES 30 5 cm MINIMUM DOUBLE MALE VENT TERMINATION ADAPTER TEE Cat III kits only FIGURE 6 TABLE 5 Category III Horizontal Venting Components Required for H...

Страница 10: ...fused disconnect switch with the fuse sized according to blower motor size Connect wiring through knockout on the junction box located on the side of the duct heater Refer to heater wiring diagram for connection information Use 18 gauge wire or larger for thermostat connections NOTE Electrically ground unit in accordance with local codes or in the absence of local codes in accordance with the curr...

Страница 11: ...hese devices should be properly labeled by the installer GAS SUPPLY TO UNIT HEATER MANUAL MAIN SHUT OFF DISCONNECT GAS VALVE WILL NOT HOLD NORMAL TEST VALVE WHEN TEST PRESSURES OF 1 2 psig PRESSURES OF 1 2 psig 3 45kPa 3 45kPa OR HIGHER OR HIGHER WILL BE USED CAP UNIT HEATER FIGURE 8 Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not u...

Страница 12: ...ttempt to light the burners manually 5 Honeywell VR8205 series turn manual knob on gas valve clockwise to OFF Do not force For White Rodgers 36 series gas valve move lever to OFF 6 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not smell gas go to next step 7 Honeywell VR8...

Страница 13: ...ximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the ACC terminals approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed Five seconds after the demand is satisfied the combustion air inducer is shut off 9 The ignition control will de energize the ACC terminals approximat...

Страница 14: ...e switch is factory set and no field adjustment is necessary Service LUBRICATION Combustion air inducer motor bearings are pre lubricated and sealed No further lubrication is necessary BURNERS 1 Periodically examine burner flames for proper appearance during the heating season 2 Before each heating season examine the burners for any deposits or blockage that may have occurred 3 Clean burners as fo...

Страница 15: ...nit unit operating 3 Check amperage draw FLUE AND CHIMNEY Check all vent and vent connector joints for tightness Ensure that connections are sealed and that there are no blockages FAILURE TO OPERATE If unit fails to operate check the following 1 Is thermostat calling for heat 2 Is main disconnect closed 3 Is there a breaker tripped or a fuse blown 4 Is gas turned on at meter 5 Is manual shutoff va...

Страница 16: ...l No Serial No Service Technician Electrical Connections Tight Air Shutters Properly Adjusted If Installed Supply Voltage Flue Connections Tight Blower Motor Lubrication O K Gas Piping Connections Tight Leak Tested THERMOSTAT Furnace Btu Input Calibrated Heat Anticipator Properly Set Line Pressure Manifold Pressure w c Level 16 ...

Страница 17: ...TEMPLATE Location of Combustion Air Inducer Mounting Holes for Rotated Inducer EXISTING HOLE EXISTING HOLE EXISTING HOLE 17 ...

Страница 18: ... credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for HED series heat exchangers For information on this product s warranty including accessing complete warranty terms registering for an extended warranty or obtaining instructions on filing a warranty claim please go to www ADPwarranty com In such states or ...

Страница 19: ...19 ...

Страница 20: ......

Отзывы: