Adp HED Series Скачать руководство пользователя страница 3

 

CSA Requirements in USA

 

 

Installation  of  gas  duct  heaters  must  conform  with  local 

building codes or, in the absence of local codes, with the 

current edition of ANSI−Z223.1, National Fuel Gas Code.

 

 

Installation  in  aircraft  hangers  must  be  in  accordance 

with  the  current  edition  of  ANSI/NFPA  No.  409, 

Standard for Aircraft Hangers.

 

 

Installation in parking structures must be in accordance 

with  the  current  edition  of  ANSI/NFPA  No.  88A, 

Standard for Parking Structures.

 

 

Installation in repair garages must be in accordance with 

the current edition of ANSI/NFPA No. 88B, Standard for

 

 

Repair Garages.

 

 

Authorities  having  jurisdiction  should  be  consulted 

before  installation.  Air  for  combustion  and  ventilation 

must  conform  to  the  methods  outlined  in  the  current 

edition of ANSI Z223.1, Section 5.3, Air for Combustion 

and  Ventilation,  or  applicable  provisions  of  local 

building codes.

 

 

The  National  Fuel  Gas  Code  (ANSI-Z223.1)  is 

available from:

 

 

American National Standard Institute Inc.

 

 

11 West 42nd Street

 

 

New York, NY 10036

 

building  codes  or,  in  the  absence  of  local  codes,  with 

the current edition of CSA-B149 installation compliance 

codes.  All  electrical  wiring  and  grounding  for  the  unit 

must  also  comply  with  the  current  edition  of  CSA 

C22.1, Canadian Electrical Code.

 

 

These  duct  heaters  are  CSA-certified  for  clearances  to 

combustible material listed on the rating plate and table 3.

 

 

Adequate  clearance  must  be  provided  around  the 

appliance and around air openings into the combustion 

chamber.  Provision  must  be  made  for  service 

accessibility.

 

 

NOTE

  −  Fire  protection  clearances  may  be  exceeded 

to provide additional space for service and accessibility.

 

 

GARAGE / WAREHOUSE INSTALLATIONS

 

 

1 −  In  a  storage  area,  clearance  from  the  heater  to 

combustible  materials  must  be  such  that  the 

combustible  material  must  not  attain  a 

temperature  above  160°F  (71°C)  during 

continuous operation of the unit.

 

 
 

WARNING

 

 

These units are CSA international design−certified. These 

duct  heaters  are  certified  for  clearances  to  combustible 

material as listed in table 1 and on unit rating plate.

 

 

Accessibility and service clearances must be observed 

in addition to fire protection clearances.

 

 

All  electrical  wiring  and  grounding  for  unit  must  be  in 

accordance with the regulations of the current edition of

 

 

ANSI/NFPA No. 70, National Electric Code.

 

 

The National Electric Code is available from:

 

 

National Fire Protection Association

 

 

1 Batterymarch Park

 

 

PO Box 9101

 

 

Quincy, MA 02269−9101

 

 

CSA Requirements in Canada

 

 

These  instructions  are  intended  only  as  a  general  guide 

and do not supersede local codes in any way. Authorities 

having jurisdiction should be consulted before installation. 

The installation must conform with local

 

 
 

2  −  Maintain  an  8−foot  (2.5  m)  minimum  clearance 

from the floor to the bottom of the heater. Refer to 

the  current  edition  of  CSA-B149  installation 

compliance codes.

 

 

AIRCRAFT HANGER

 

 

1 −  In an area where aircraft are housed or serviced, 

a  10-foot  (3m)  minimum  clearance  from  the 

highest  surface  of  the  aircraft  to  bottom  of  the 

heater must be maintained.

 

 

2 −  In  other  areas,  an  8-foot  (2.5m)  minimum 

clearance from the floor to bottom of heater must 

be maintained.

 

 

TABLE 1

 

UNIT CLEARANCES TO COMBUSTIBLE MATERIALS

 

 

 

  

Top

 

Sides

 

 

Bottom

 

 

 

Rear

 

 

Flue

 

 

Model

 

   

 

 

 

 

 

 

 

 

 

 

 

in

 

 

mm

 

in

 

 

mm

 

in

 

 

mm

 

in

 

 

mm

 

in

 

 

mm

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HED−75

 

 

1

 

 

25

 

6

 

 

152

 

0

 

 

0

 

18

 

 

457

 

6

 

 

152

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HED−100

 

 

6

 

 

152

 

6

 

 

152

 

0

 

 

0

 

18

 

 

457

 

6

 

 

152

 

 

through −300

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Combustible  materials  that  are  affected  by 

exposure  to  temperatures  less  than  160°F 

(plastics,  plastic  wrap,  styrofoam,  cardboard, 

etc.)  must  be  stored  well  away  from  this 

heater.  Discharge  air  temperatures  for  these 

units can approach 200°F.

 

3

Содержание HED Series

Страница 1: ...mplate 17 Warranty 18 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exact ly could result in serious injury death or property damage Be sure to read and understand the installation operation and service instructions in this manual Improper installation adjustment alter ation service or maintenance can cause serious injury death or...

Страница 2: ... in 31 5 16 32 3 16 41 1 8 3 11 16 40 17 1 2 3 1 4 25 39 1 8 15 3 8 35 1 16 9 HED 250 A S mm 795 817 1045 97 1016 445 83 635 994 391 891 229 HED 300 A S A Heat Exchanger Aluminum Steel S Heat Exchanger Stainless Steel Shipping The heater is completely assembled and is shipped with installation and operating instructions warranty certificate and flue transition Check the unit for shipping damage Th...

Страница 3: ...e area clearance from the heater to combustible materials must be such that the combustible material must not attain a temperature above 160 F 71 C during continuous operation of the unit WARNING These units are CSA international design certified These duct heaters are certified for clearances to combustible material as listed in table 1 and on unit rating plate Accessibility and service clearance...

Страница 4: ...onnection and not less than 2 equivalent diameters in length See figure 1 SINGLE BLOWER APPLICATION Top View 155 TRANSITION HED UNIT BLOWER AIR FLOW DUCT LENGTH L The formula for computing duct length L is 4WH W WidthH Height Inlet W H Duct length L is computed as shown by the formula and rounded to the nearest whole number MODEL INLET DUCT in mm DUCT NO WIDTH HEIGHT LENGTH L HED 75 15 13 3 8 29 3...

Страница 5: ... rotate the combustion air inducer on HED models 200 250 and 300 Rotate the combustion air inducer assembly as follows 1 Remove the heater from the carton Decide the best duct heater orientation The vent can be installed in one of three discharge positions up left or right 2 If the inducer is to be rotated follow the instructions in this section otherwise refer to instructions under Venting sectio...

Страница 6: ...l HED duct heaters are listed as Category 1 appliances for vertical vent installations 1 All HED duct heaters are to be used with NFPA or ANSI approved chimneys or U L listed type B 1 gas vents where applicable as well as the modifications and limitations listed in figure 2 Seal single wall vent material according to General Recommendations and Requirements section 2 Keep the vent connector runs a...

Страница 7: ...ct heater If the HED duct heater is to be horizontally vented a positive pressure may be created in the vent The duct heater when installed with horizontal venting will perform as a category III appliance 1 Special vent materials approved for use with Category III appliances may be used with these units Refer to table 7 for venting components 2 If possible do not terminate the horizontal vent thro...

Страница 8: ...he vent termination if permitted by authorities Fig 5 13 For horizontal venting the vent pipe must be supported with hangers no more than 3 feet 1m apart to prevent movement after installation 14 All horizontal vent applications which use Category III vent pipe must terminate with an approved Category III tee Opening end must face downward 15 When termination is routed through an exterior combusti...

Страница 9: ...ructions OR listed special vent for Category III appliances SLOPE 1 4 IN PER FOOT RUN MAXIMUM NOTE Minimum horizontal length equals 5 feet 1 53 m This does not include termination tee Refer to table 6 for maximum length and number of elbows 12 INCHES 30 5 cm MINIMUM DOUBLE MALE VENT TERMINATION ADAPTER TEE Cat III kits only FIGURE 6 TABLE 5 Category III Horizontal Venting Components Required for H...

Страница 10: ...fused disconnect switch with the fuse sized according to blower motor size Connect wiring through knockout on the junction box located on the side of the duct heater Refer to heater wiring diagram for connection information Use 18 gauge wire or larger for thermostat connections NOTE Electrically ground unit in accordance with local codes or in the absence of local codes in accordance with the curr...

Страница 11: ...hese devices should be properly labeled by the installer GAS SUPPLY TO UNIT HEATER MANUAL MAIN SHUT OFF DISCONNECT GAS VALVE WILL NOT HOLD NORMAL TEST VALVE WHEN TEST PRESSURES OF 1 2 psig PRESSURES OF 1 2 psig 3 45kPa 3 45kPa OR HIGHER OR HIGHER WILL BE USED CAP UNIT HEATER FIGURE 8 Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not u...

Страница 12: ...ttempt to light the burners manually 5 Honeywell VR8205 series turn manual knob on gas valve clockwise to OFF Do not force For White Rodgers 36 series gas valve move lever to OFF 6 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not smell gas go to next step 7 Honeywell VR8...

Страница 13: ...ximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the ACC terminals approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed Five seconds after the demand is satisfied the combustion air inducer is shut off 9 The ignition control will de energize the ACC terminals approximat...

Страница 14: ...e switch is factory set and no field adjustment is necessary Service LUBRICATION Combustion air inducer motor bearings are pre lubricated and sealed No further lubrication is necessary BURNERS 1 Periodically examine burner flames for proper appearance during the heating season 2 Before each heating season examine the burners for any deposits or blockage that may have occurred 3 Clean burners as fo...

Страница 15: ...nit unit operating 3 Check amperage draw FLUE AND CHIMNEY Check all vent and vent connector joints for tightness Ensure that connections are sealed and that there are no blockages FAILURE TO OPERATE If unit fails to operate check the following 1 Is thermostat calling for heat 2 Is main disconnect closed 3 Is there a breaker tripped or a fuse blown 4 Is gas turned on at meter 5 Is manual shutoff va...

Страница 16: ...l No Serial No Service Technician Electrical Connections Tight Air Shutters Properly Adjusted If Installed Supply Voltage Flue Connections Tight Blower Motor Lubrication O K Gas Piping Connections Tight Leak Tested THERMOSTAT Furnace Btu Input Calibrated Heat Anticipator Properly Set Line Pressure Manifold Pressure w c Level 16 ...

Страница 17: ...TEMPLATE Location of Combustion Air Inducer Mounting Holes for Rotated Inducer EXISTING HOLE EXISTING HOLE EXISTING HOLE 17 ...

Страница 18: ... credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for HED series heat exchangers For information on this product s warranty including accessing complete warranty terms registering for an extended warranty or obtaining instructions on filing a warranty claim please go to www ADPwarranty com In such states or ...

Страница 19: ...19 ...

Страница 20: ......

Отзывы: