INSTRUMENT RESPONSE TIMES
The instrument, to satisfy most requests, uses a variable time in accordance with the programming of
the instrument parameters and the type of request as per table:
Update frequency of measurements
12,5 Hz
50 Hz
100 Hz
250 Hz
1000 Hz
Analogue output update frequency
12,5 Hz
50 Hz
100 Hz
250 Hz
1000 Hz
Fieldbus memory area reading and
update update frequency.
125 Hz
125 Hz
125 Hz
125 Hz
125 Hz
Update frequency of logic outputs.
12,5 Hz
50 Hz
100 Hz
250 Hz
1000 Hz
Status and weight acquisition cycle from
Modbus RTU (*)
𝒇𝒇𝒇𝒇𝒇𝒇𝒇𝒇
=
𝟏𝟏
𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏
+
∗
𝟖𝟖
𝟏𝟏𝟏𝟏𝒃𝒃𝒃𝒃𝒃𝒃𝒃𝒃
+
,
𝟎𝟎 𝟎𝟎𝟎𝟎𝟎𝟎
Status and weight acquisition cycle from
ASC11 protocol (*)
𝒇𝒇𝒇𝒇𝒇𝒇𝒇𝒇
=
𝟏𝟏
𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏𝒏
+
𝟖𝟖 ∗ 𝟏𝟏𝟏𝟏
𝒃𝒃𝒃𝒃𝒃𝒃𝒃𝒃
+
,
𝟎𝟎 𝟎𝟎𝟎𝟎𝟎𝟎
(*) nchar = sum of characters which make up the request string of the master (Query) and the response
string of the T200F (Response).
Example of status request, net weight and gross weight (5 registers) at baud rate = 115,2 kbit/sec:
1 / (((8 + 15 + 8) * 10) / 115200) + 0,004) = 149 Hz
Exceptions are:
• the Backup E2prom command (max time = 350mSec.)
• writing of the registers of Cells capacity, Cells sensitivity, Net weight, System tare, Filter (max time
= 550mSec).