Temperature Controller ETA 110
_________________________________________________________________________________________________________
_________________________________________________________________________________
04.06.09 page 4
Use the buttons „outer right“ to set the difference values. Display shows „d1“ or
„d2“. Now make your entry, in a range from 0 to 100°C, using the arrow buttons.
Setting the upper temperature limit: Code 302
Display shows „HIG“
Range from 30°C to 400°C
Software version is shown (for a few seconds): Code 678
(e.g. Uer 10.0)
Digital offset adjustment: Code 777
The temperature sensor is shown in the upper left display „1“ or „2“.
Use the outer left button -
„2“ has no meaning.
The actual current temperature is shown in the lower display. The upper left
display shows the value of the hundreds.
Make the offset adjustment by using the „Plus“ and „Minus“ buttons
Load default factory setting: Code 993
(display “InI“)
Load by using the outer left button
Standard default settings are:
-
Code 100 „left outer“ button not active (OFF)
-
Code 101 : heating
-
Code 102 : upper-/lower limit (Limit comparators)
-
Code 111: 2-point, 1°C hysteresis
-
Code 113: 0°C
-
Code 119: OFF
-
Code 302: 400°C
Connection diagram
:
Error messages:
Malfunctions of the temperature sensor are shown in the display for the actual temperature:
„EEE“
means sensor break
„- - - „
means short circuit in the sensor
ETA 110
230V AC
PE L1 N
04
03
02
01
08
07
06
05
12
11
10
09
14
13
K1: heating or cooling
K2: upper-/lower value,
operation or signal
chamber
Pt100
K2
K1