Temperature Controller ETA 110

  

_________________________________________________________________________________________________________

 

_________________________________________________________________________________ 
04.06.09                                                                                                                                         page 4 

 
Use the buttons „outer right“ to set the difference values. Display shows „d1“ or 
„d2“. Now make your entry, in a range from 0 to 100°C, using the arrow buttons. 

 

Setting the upper temperature limit:  Code 302 

Display shows „HIG“ 

                     Range from 30°C to 400°C 
 

Software version is shown (for a few seconds): Code 678  

(e.g. Uer 10.0) 

 

Digital offset adjustment: Code 777 

                     

The temperature sensor is shown in the upper left display  „1“ or „2“.  

                       Use the outer left button  - 

„2“ has no meaning. 

The actual current temperature is shown in the lower display. The upper left 
display shows the value of the hundreds.                 

                     

Make the offset adjustment by using the  „Plus“ and „Minus“ buttons 

 

Load default factory setting: Code 993  

(display “InI“)   

                      Load by using the outer left button 
                     Standard default settings are: 

-

 

Code 100 „left outer“ button not active (OFF) 

-

 

Code 101 : heating 

-

 

Code 102 : upper-/lower limit (Limit comparators) 

-

 

Code 111: 2-point, 1°C hysteresis 

-

 

Code 113: 0°C 

-

 

Code 119: OFF 

-

 

Code 302: 400°C 

 
 
Connection diagram

 
 
 
 
 
 
 
 

 
 
 
 
Error messages: 

 
Malfunctions of the temperature sensor are shown in the display for the actual temperature:  

„EEE“

  means sensor break 

„- - - „ 

 means short circuit in the sensor 

 
 
 
 

 

ETA 110 

 

230V AC 

PE        L1   N 

04

 

03

 

02

 

01

 

08

 

07

 

06

 

05

 

12

 

11

 

10

 

09

 

14

 

13

 

K1: heating or cooling 
K2: upper-/lower value,  
      operation or signal 

 

chamber 
Pt100 

 

K2 

 

K1 

 

Содержание ETA 110

Страница 1: ...nd the nominal temperature in the lower display As soon as the controller has been connected to the mains it is in operating mode Please note also see setting options under code 100 The nominal temperature can be set within the programmed limits by using the Plus and Minus buttons Code entry press the two buttons on the outer left and right simultaneously for ca 3 seconds The lower display will sh...

Страница 2: ...e interchanged and off functions are not interchanged The relay displays in codes 101 and 102 will be changed accordingly Basic setting off The function of the heating control Code 111 can be pre set for example to avoid exceeding the nominal value There are three options of how to set the heating control 2 point controller When the actual value reaches the nominal value the output relay will swit...

Страница 3: ...Setting the upper and lower limits limit comparators Code 113 Display shows LCo Upper display shows difference to the nominal temperature value Minus sign in front of the number lower limit Plus sign in front of the number upper limit Setting and activating the 3 levels heating Code 119 The graded 3 level heating has a nominal temperature value and two difference values These difference values for...

Страница 4: ...e the outer left button 2 has no meaning The actual current temperature is shown in the lower display The upper left display shows the value of the hundreds Make the offset adjustment by using the Plus and Minus buttons Load default factory setting Code 993 display InI Load by using the outer left button Standard default settings are Code 100 left outer button not active OFF Code 101 heating Code ...

Страница 5: ...ielding and that this shielding is connected to the sensor housing itself 5 Relay outputs The relay outputs are potential free and the maximal load of 250V AC and 4A must not overshoot 6 Water and humidity Never use the unprotected appliance near water e g near a bath tub water basin sink washing machine a damp cellar or near a swimming pool The appliance is only waterproof on the front IP67 The b...

Страница 6: ..._____ 04 06 09 page 6 For any questions orders and repairs please contact our customer service team at the address below Measurment control Process controls Hardware development Software development Specialized electronics Food Technology Process Visualization aditec gmbh Talweg 17 D 74254 Offenau Tel 49 0 7136 96122 0 Fax 49 0 7136 96122 20 www aditec net eMail info aditec net aditec CONTROLS for...