17.6.2 Flue draught stabilizer
In case of excessive draught / depression (this can cause vibrations in the
chimney), or a chimney with fan for flues diluted with air, you have to install a flue
draught stabilizer inside the chimney.
In this case, you have to install a stabilizer for each boiler to guarantee the
correct draught of the chimney in all the boiler operating modes: at the minimum
power, at the maximum power and at intermediate points.
Example of a flue draught stabilizer:
Example 1: installation with 1 boiler
5
1
4
2
3
6
7
Legend:
1. Boiler
2. Horizontal section connected to the boiler flues outlet (it should be as shortest as possible and with the minimum
number of elbows)
3. “T” chimney
4. Draining: outlet of condensate and rain water
5. Flue draught stabilizer
6. Vertical section of the chimney
7. Chimney outlet
8. Connection between boilers and flues collector
9. “T” to connect the flues collector to each boiler
10. Flues collector (we recommend that it has an upward slope up to the vertical section of the chimney, min. 3%)
CAUTION: Check that no flues are getting outside through the damper (5). Damage may be caused to people.
It is a responsability of the installation company to check and ensure the proper operation of this matter. The
manufacturer of the boilers declines any responsability for these matters.
17.6.3 Old installation
-
If using a metallic and insulated chimney already existing, before installing the boiler it is advisable to verify that
the chimney has the right dimensions to allow a correct evacuation of the burnt gases and an easy cleaning of its
interior.
-
In case of using a brick chimney already existing, it is necessary to fit it with an internal metal casing in order to
avoid water condensing in all its length. If it is not possible to do it, it is advisable to install a new insulated
chimney, preferably made of stainless steel and in accordance with the current regulations.
1
7
5
5
4
2
3
1
4
2
3
6
1 0
9
8
8
9
Example 2: installation with two boilers and
one common chimney (see regulations)
Содержание ADI CD 375
Страница 1: ...1 º º ADI CD CONDENSING BOILER TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE V 07 2017 ...
Страница 7: ...ADI CD boiler Technical Manual 7 Models ADI CD 200 and higher A C D B J H G F E R S ...
Страница 34: ...ADI CD boiler Technical Manual 34 12 1 Electric drawing ADI CD 70 750 ...
Страница 35: ...ADI CD boiler Technical Manual 35 12 2 Electric drawing ADI CD 850 950 ...