![Adisa ADI CD 375 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/adisa/adi-cd-375/adi-cd-375_technical-manual-of-installation-use-and-maintenance_2851531046.webp)
ADI CD boiler - Technical Manual
46
MC shifting, PC absolute
The pump heating circuits stay locked until the DHW storage tank is heated up. If the capacity of the heat source is
not sufficient, the mixing heating circuits will be restricted also.
Legionella function
When the Legionella function (1640) is activated, the DHW storage tank temperature is periodically raised to the
Legionella function setpoint.
Off
Function is deactivated.
Periodically
The Legionella function is repeated according to the selected interval (1641). If the Legionella setpoint is attained via
solar heating – independent of the selected interval – the time period is started again.
This means that the heat source is switched on only if the solar plant was not able to ensure the required Legionella
function setpoint within the set period of time.
Fixed weekday
The Legionella function can be activated on a fixed weekday (1642). When using this setting, heating up to the
Legionella setpoint takes place on the selected weekday, independent of previous storage tank temperatures.
Guide Values:
Storage tank
temperature
Dwelling time
80 °C
A few seconds
70 °C
1 minute
66 °C
2 minutes
60 °C
32 minutes
55 °C
6 hours
50 °C
No killing of viruses
45 °C
Ideal conditions for viruses
Warning!
The figures given in the table are guide values. They do not guarantee that
Legionella viruses will be completely killed.
Warning!
During the time the of the Legionella function, there is a risk of scalding
when opening the taps.
Содержание ADI CD 375
Страница 1: ...1 º º ADI CD CONDENSING BOILER TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE V 07 2017 ...
Страница 7: ...ADI CD boiler Technical Manual 7 Models ADI CD 200 and higher A C D B J H G F E R S ...
Страница 34: ...ADI CD boiler Technical Manual 34 12 1 Electric drawing ADI CD 70 750 ...
Страница 35: ...ADI CD boiler Technical Manual 35 12 2 Electric drawing ADI CD 850 950 ...