ADI CD boiler - Technical Manual
51
17.6 Chimneys
The flues outlet, according to the current rules, must ensure a correct evacuation of the burnt gases, without
backward flows and without producing condensate. The natural draught of the chimney must evacuate the burnt
gases from the boiler flues outlet.
17.6.1 Chimney sizing
The internal diameter depends on:
- Heat input of the boilers, type, number of boilers installed and water working temperatures.
- Type of gas.
- Chimney: vertical height, horizontal length (minimum slope: 3 to 5%).
- Number of elbows and their angles (they should be reduced to the minimum).
- The chimney material and if it is insulated or not.
If several boilers are connected to the same chimney, it is important to consider the distance between them and the
dimensions of the flue header.
The base of the vertical chimney must include a drainage pipe to evacuate the condensate.
With regard to boilers, these are the data to be considered for calculation:
-
Values of CO
2
, for Natural Gas: it is recommended to adjust CO
2
at 8.1%, for all the boilers
Models
Range CO2 (%) for Natural Gas
ADI CD 70 to 120
7.3 - 9.3%
ADI CD 120 to 175
7.2 - 8.7%
ADI CD 200 to 250
7.3 - 8.8%
ADI CD 325 to 550
7.6 - 8.6%
ADI CD 850 to 950
7.7 - 9.0%
- Flues temperature:
Flues temp.
MAXIMUM POWER
MINIMUM POWER
Average Water temperature
High (70ºC)
Low (40ºC)
High (70ºC)
Low (40ºC)
Flues Temp.
70 - 80ºC
50 - 60ºC
60 - 70ºC
40ºC
- Residual pressure at the boiler flues outlet:
Model
ADI CD
Ø boiler flue outlet
External diam. (mm)
MAXIMUM POWER
MINIMUM POWER
Power Input
kW
Residual Pressure
(Pa)
Power Input
kW
Residual Pressure
(Pa)
70
150
72.7
42.0
21.8
2.5
85
150
87.7
37.8
26.3
7.5
105
150
107
90.0
32
40.0
120
150
123
64.8
37
5.0
175
150
166
54.0
49.8
10.0
200
175
202.2
60.0
60.7
7.5
250
175
246.5
81.0
74
8.5
325
250
300.5
90.0
90.2
20.0
375
250
361.2
64.8
108.4
7.5
450
250
448
90.0
134
45.0
550
350
546
72.0
163.9 (*)
10.0
650
350
618
75.0
185.4 (*)
10.0
750
350
700
78.0
210 (*)
7.5
850
350
818.5
177.5
327.4
24.7
950
350
924.5
266.2
369.8
39.4
(*) Minimum power adjustable up to 30% of the gas power: to be adjusted onsite in the installation (during commissioning), according to the installation conditions.
Содержание ADI CD 375
Страница 1: ...1 º º ADI CD CONDENSING BOILER TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE V 07 2017 ...
Страница 7: ...ADI CD boiler Technical Manual 7 Models ADI CD 200 and higher A C D B J H G F E R S ...
Страница 34: ...ADI CD boiler Technical Manual 34 12 1 Electric drawing ADI CD 70 750 ...
Страница 35: ...ADI CD boiler Technical Manual 35 12 2 Electric drawing ADI CD 850 950 ...