2.2 Uplink Frame format
2.2.1 Product configuration (0x10)
This frame is sent following the reception of a frame with code 0x01, or at the start of the product.
Offset
(in byte)
Data
Description
0
0x10
Frame code
1
Status
Status byte
2-3
S300
Transmission period of the Keep Alive frame
4-5
S301
Transmission period of the periodic frame
6-7
S320
History period
8-9
S321
Sampling period
10-11
S322
Inhibition time
Decoding example:
Offset
(in byte)
Data
Description
0
0x10
Frame code
1
0x00
Frame counter: 0
Bit1@0: no LowBat
2-3
0x21C0
8640 => 8640 x 10s = 86400s = 24h
4-5
0x0001
1
6-7
0x0001
1
8-9
0x0708
1800 => 1800 x 2s = 3600s = 1h
10-11
0x001E
30 => 30 x 10s = 300s = 5min
2.2.2 Digital inputs configuration (0x1F)
This frame is sent at the start of the product if at least one digital input is activated
Offset (in byte)
Data
Description
0
0x1F
Frame code
1
Status
Status byte
2
S380
Configuration of the button alarm (digital input 1)
3-4
S381
Threshold of the alarm button (digital input 1)
5
S382
Configuration of the digital input 2
6-7
S383
Threshold of digital input 2 alarm
Decoding example:
Offset (in byte)
Data
Description
0
0x1F
Frame code
1
0x00
Frame counter: 0
Bit1@0: no LowBat
2
0x41
EVENT ON/OFF, debound@100ms
3-4
0x0001
Alarm triggered after one detection
5
0x00
No alarm configured for digital input 2
6-7
0x0000
No threshold value