Section 14 – Access Control
14-3
+
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
POLE Door Strike/Mag Coil
DATA 1 (WHITE)
DATA 0 (GREEN)
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
+5V
GND
TRIGGER (SEE NOTE 3)
+12V (RED)
ZONE C (General)
ZONE A (DSM)
ZONE B (RTE)
POLLING LOOP -
14V MAX (12V @ 85-160mA Nominal)
POLLING LOOP +
GND
GND
GND
N/O DOOR STRIKE POWER
N/C MAG COIL POWER
2
3
4
5
6
7
8
11 12
2 3 4 5 6 7 8 9 10
1
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
TB 1
TB 3
1
READER INTERFACE CABLE
GND (BLACK)
RDR LED (ORANGE)
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
NO
CONNECTION
VISTAKEY
THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
K1
DOOR
CONTROL
RELAY
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
TO TB1, 11 OR 12
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
Figure 14-1: Wiring the VistaKey
Connecting the Card Reader
Lead from Reader
Lead Color
To VistaKey TB3
Terminal #
Green LED
Orange
1
Ground*
Black
2
DATA 1 (Clock)
White
3
DATA 0 (Data)
Green
4
+5VDC†
Red†
6
+12VDC†
Red†
7
* TB-3 Terminal 5 is also a ground and may be used instead of
terminal 2. Terminals 2 and 5 are a common ground.
Connect to +5VDC OR +12VDC per reader manufacturer’s
specification.
Содержание VISTA-128B
Страница 2: ...ii...
Страница 10: ...VISTA 128B Installation and Setup Guide x...
Страница 26: ...VISTA 128B Installation and Setup Guide 3 4...
Страница 34: ...VISTA 128B Installation and Setup Guide 5 4...
Страница 40: ...VISTA 128B Installation and Setup Guide 6 6...
Страница 54: ...VISTA 128B Installation and Setup Guide 8 8...
Страница 64: ...VISTA 128B Installation and Setup Guide 10 4...
Страница 104: ...VISTA 128B Installation and Setup Guide 18 8...
Страница 112: ...VISTA 128B Installation and Setup Guide 20 4...
Страница 132: ...VISTA 128B Installation and Setup Guide 22 18...
Страница 160: ...VISTA 128B Installation and Setup Guide 25 6...
Страница 166: ...VISTA 128B Installation and Setup Guide 27 2...
Страница 180: ...VISTA 128B Installation and Setup Guide 29 8...
Страница 186: ...VISTA 128B Installation and Setup Guide 30 6...
Страница 191: ...B 1 A P P E N D I X B DIP Switch Tables...
Страница 194: ...VISTA 128B Installation and Setup Guide B 4...
Страница 198: ...VISTA 128B Installation and Setup Guide D 2...
Страница 208: ...9 l K3271V1 9 00 165 Eileen Way Syosset New York 11791 Copyright 1999 PITTWAY CORPORATION...