VISTA-128B Installation and Setup Guide
22-2
*14
ZONE 9 RESPONSE TIME
[0]
Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zone 9.
Enter 0 for normal response (350 msec). Must be 0 for UL.
*15
KEYSWITCH ASSIGNMENT
[0]
Enter the partition number 1-8 in which the keyswitch is being used. Otherwise, enter
0.
Requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone
when used for keyswitch operation). If the keyswitch is used, the fire and panic alarm
voltage triggers automatically become ARMING and READY status outputs for support
of the Keyswitch LEDs.
Reports openings/closing by user "0" if reporting is enabled in field *40.
*16
CONFIRMATION OF ARMING DING (part.-specific)
[0]
Enter 1 to enable 1/2 second external alarm sounding ("ding") at the end of exit delay (or
after kissoff from the central station, if sending closing reports). Otherwise enter 0.
Must be 1 for UL commercial burglary installations. Bell test on arming is required in
UL commercial burglary installations.
*17
AC LOSS KEYPAD SOUNDING
[0]
Enter 1 to enable sounding at the keypad (rapid beeping) when AC power is lost
(sounding occurs about 2 minutes after actual AC loss).
Enter 0 if no AC power loss keypad sounding is desired.
*19
RANDOMIZE AC LOSS REPORT
[0]
Selecting this option helps prevent an overload of AC loss messages at the central
station during a community blackout.
Enter 1 to randomize AC loss reporting between 10 and 40 min. after an actual AC loss.
Enter 2 for 6-12 hours after AC loss. Enter 0 for normal AC loss reporting (about 2
minutes after actual AC loss).
*20
VIP MODULE PHONE CODE
[00, 11]
|
|
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code used to access
the system.
Enter 01-09 for first digit, and enter 11 (for
✴
) or 12 (for #) for second digit.
To disable the voice module, enter 00 for the 1st digit and enter 11 for the 2nd digit of
the code (disable code = 00,11). Must be disabled for commercial fire and UL
commercial burglary installations.
*21
PREVENT FIRE TIMEOUT
[0]
Enter 1 to disable (no timeout) the alarm sounder duration for any zone designated as a
fire zone, regardless of partition, so that fire sounding continues until the system is
reset.
Enter 0 if the normal burglary sounder duration (programmed in partition-specific field
*13) should apply to fire alarms.
*22
KEYPAD PANIC ENABLES (partition-specific)
[001]
|
|
95
96
99
Enter 1 to enable the appropriate keypad panics used in this partition.
Otherwise enter 0.
Содержание VISTA-128B
Страница 2: ...ii...
Страница 10: ...VISTA 128B Installation and Setup Guide x...
Страница 26: ...VISTA 128B Installation and Setup Guide 3 4...
Страница 34: ...VISTA 128B Installation and Setup Guide 5 4...
Страница 40: ...VISTA 128B Installation and Setup Guide 6 6...
Страница 54: ...VISTA 128B Installation and Setup Guide 8 8...
Страница 64: ...VISTA 128B Installation and Setup Guide 10 4...
Страница 104: ...VISTA 128B Installation and Setup Guide 18 8...
Страница 112: ...VISTA 128B Installation and Setup Guide 20 4...
Страница 132: ...VISTA 128B Installation and Setup Guide 22 18...
Страница 160: ...VISTA 128B Installation and Setup Guide 25 6...
Страница 166: ...VISTA 128B Installation and Setup Guide 27 2...
Страница 180: ...VISTA 128B Installation and Setup Guide 29 8...
Страница 186: ...VISTA 128B Installation and Setup Guide 30 6...
Страница 191: ...B 1 A P P E N D I X B DIP Switch Tables...
Страница 194: ...VISTA 128B Installation and Setup Guide B 4...
Страница 198: ...VISTA 128B Installation and Setup Guide D 2...
Страница 208: ...9 l K3271V1 9 00 165 Eileen Way Syosset New York 11791 Copyright 1999 PITTWAY CORPORATION...