background image

IRIS-4 160

 

Quick Installation and

Maintenance Guide

IRIS-4 160

7

6

6.1. Mounting

Choose a suitable location, taking into consideration 
the routing of both power and dialler interface cables . 
To remove the cover push the two release prongs on 
the underside of the plastic case as indicated on the 
back of the case .

Once released, lift the lid slightly and push up until 
lid comes off, remove the dialler PCB (retained by 
two clips to left and right off the board) . Position the 
housing on the wall and drill three holes . Feed the ca-
bles through the opening at the base of the plate, or 
via the ‘knockouts’, and secure the plate to the wall 
with the three screws supplied .

Slide the PCB back into the top retainers and within 
the side pillar and then gently secure the dialler back 
in place using the release clips .

Now secure the bottom part of the PCB using the 2 
screws and washers supplied as shown in the image 
below, to comply with EN 50131-1:2006+A2:2017: 

6. InStaLLIng the IRIS-4 160 DIaLLeR

6.2. Power

Power using a 9-17V DC power supply specified to 
deliver a minimum of 1A current, and can use either 
screw terminals or TTL header indicated in Section 4 
“Board Configuration” .

Note: For Radio Equipment Directive compliance, 
the power cable must be no longer than 3 meters 
in length.

Fit the power cable . DO NOT APPLY POWER TO 
THE DIALLER UNTIL INDICATED .

6.3. Backup Batteries (optional)

Designed to continue reporting to the IRIS Secure 
Apps System at the Monitoring Centre to maintain 
confidence of link status in the case of a main power 
source failure . The design provides over 15 hours 
battery support with 15 minute polling across either 
Ethernet, Wi-Fi or 4G/3G/2G . 

Note: Battery support could be shorter than the 15 
hours if the polling period is shortened or other 
activities such as alarm alerting by the panel at 
regular intervals.

If batteries are required, DO NOT FIT until indicated 
in Section 6 .9 “Configuration” .
Use Batteries approved to IEC61951-2 (EN 61951-2) .
The IRIS-4 160 requires 4 x 1 .5V NiMh AA size 
rechargeable batteries (not included) .
Recommended manufacturers/types are:
•  GP ReCyko 210AAHCB
•  Annsman maxE 2100

Note: Do not use other battery types – including 
non-rechargeable batteries.

The required battery capacity is 2000mAH minimum 
and ideally they should feature low self-discharge .
Maximum time to recharge to 80% = 32 Hours .
Overvoltage protection triggered at 6 .5V DC, with a 
deep discharge protection of 4V DC .

Note: Reduced system standby life and battery life 
if lower quality batteries fitted, not recommended.

6.4. Connections

Connect cables to the PCB for the system as shown 
on in Section 4 “Board Configuration”: 
•  Ethernet enabled systems: Connect the ‘ETH’ 
 

connector using the Ethernet cable to the local 

 

IP router/switch or socket that allocated for the 

 

LAN/WAN network IP connection .

•  Wi-Fi: Wi-Fi (wireless) 2.4GHz b/g/n internal 
 

PCB chip antenna .

•  4G/3G/2G enabled systems: 4G/3G/2G antenna 
 

already fitted to board .

•  Dial capture port (optional and for more 
 

information see section below) .

•  4 x Pin inputs (optional for more information 
 

see section below) .

Optional Serial Connection

The following three connections to alarm panel are 
available .
•  RS485 currently available for Honeywell Galaxy  
 

data bus (Alarms and Upload/download) or  

 

Risco ProSys bus (Upload/download) connec-

 

tions (optional) .

•  Serial (TTL) currently available for Texecom  
 

Com1 connections (optional) .

•  RS232 screw terminal (optional).

Note 1: For Radio Equipment Directive compliance, 
any interconnecting cable (Dial capture, Pin inputs 
or Serial connection) must be no longer than 3 
meters in length.

Note 2: Please refer to the IRIS-4 160 Engineering 
Manual for wiring and connections information 
available from http://www.addsecure.com 

Fixing Screw

Содержание IRIS-4 160

Страница 1: ...AIRBORNE DC MEDIUM Hurtigmanual Snabbguide IRIS 4 160 Quick Installation and Maintenance Guide...

Страница 2: ...mission System ATS configuration up to SP3 for single path or ATS configuration DP2 for dual path The IRIS 4 160 is based on the successful IRIS Touch NG range of AoIP diallers with the same hardware...

Страница 3: ...en the following information will not be required as it will be assigned by the network IP address Gateway address Subnet mask address Wi Fi Connection Details The customer s Wi Fi network details are...

Страница 4: ...tened or other activities such as alarm alerting by the panel at regular intervals If batteries are required DO NOT FIT until indicated in Section 6 9 Configuration Use Batteries approved to IEC61951...

Страница 5: ...s the equivalent restore signal Via Sense Resistors It is also possible to link the contacts to the IRIS 4 160 dialler via sense resistors so that an open or short circuit tamper on the loop is detect...

Страница 6: ...local Configuration viaWeb Browser usingWi Fi Connection Can be configured using the Wi Fi connection using a standard Web browser from any smartphone tablet or laptop device and supports the followin...

Страница 7: ...and follow the on screen prompts Note 1 If installing the IRIS 4 160 without batteries then please untick the Use battery backup option Note 2 During the Installation Wizard the Wi Fi status screen a...

Страница 8: ...heck battery status and replace if below required level Reflash IRIS 4 160 software to latest version Test the configured communication paths Ethernet Wi Fi 4G 3G 2G Perform full test of alarms from t...

Страница 9: ...atteries fitted for backup purpose replaced them every two years 7 4 Check SoftwareVersion Reflash Go to the settings menu and then select Latest software this will then check with the AddSecure Refla...

Страница 10: ...up impedance 10K to 3 3V supply Alarm protocols SIA level 1 to 3 reference SIA DC 03 1990 01 R2003 10 Contact ID reference SIA DC 05 1999 09 Fast format Scancom for dial capture and serial connection...

Страница 11: ...s are connected to avoid safety hazards SELV SELV Safety Extra Low Voltage is defined as a secondary circuit which is so designed and protected that under normal and single fault conditions the voltag...

Отзывы: