![ADC Soneplex Soneplex Fiber Hub Cabinet SPX-CABFIN04 Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/adc/soneplex-soneplex-fiber-hub-cabinet-spx-cabfin04/soneplex-soneplex-fiber-hub-cabinet-spx-cabfin04_user-manual_2848187066.webp)
Installation
LTPS-UM-8007-01, Issue 1
54
November 9, 2001
SPX-CABFIN01, SPX-CABFIN04
C
ONFIGURING
A
LARMS
Alarms are wired to a wire-wrap cross-connect panel. Refer to cabinet drawing T-CS405-30 (furnished with
cabinet) for a summary of all cabinet alarms and their physical terminations.
For a summary of the more important cabinet and power alarms and their activators, refer to
Table 7.
Alarm Summary
Alarm Designation
Alarm Activator
RFA
Activated by the absence of rectifier DC output. Could be caused by: AC input failure, AC
INPUT circuit breaker operation, or high voltage shutdown (over -59.5 Vdc). (To reduce
the possibility of a false RFA, there is a self-test interval of 20 to 40 seconds between
detection and the issuance of local and remote RFAs.)
CB CR
Activated by one or both of the following conditions:
•
Manual or automatic operation of the DC OUTPUT circuit breaker on either rectifier.
•
Manual or automatic opening of two or more DC load circuit breakers (on the DC
distribution panel).
AC FAIL
Indicates the absence of 240 Vac power to the rectifiers and battery heaters.
LVD
(Low Voltage Disconnect) Activated when the battery string voltage drops to -42.5 Vdc,
signaling the imminent disconnection of that battery string (and system failure if the
cabinet is on backup power).
AUX FA
Indicates failure of one or more fuses in the Auxiliary Fuse and Alarm Panel. These fuses
control critical equipment in the cabinet (heat exchanger fans, intrusion alarms, and
auxiliary fan shelves).
INTRUSION
Indicates that a door is open (or closed improperly) and the available 30-minute delay
has expired or was not initiated.
HI TEMP
Indicates that the temperature inside the main chamber has exceeded 150°F (66°C).
Reset when the temperature decreases to 130°F (54°C).
Содержание Soneplex Soneplex Fiber Hub Cabinet SPX-CABFIN04
Страница 1: ...Soneplex Soneplex USER MANUAL Soneplex Fiber Hub Cabinet Product Catalog SPX CABFIN01 SPX CABFIN04...
Страница 6: ...Cautions and Warnings LTPS UM 8007 01 Issue 1 vi November 9 2001 SPX CABFIN01 SPX CABFIN04...
Страница 12: ...List of Tables LTPS UM 8007 01 Issue 1 xii November 9 2001 SPX CABFIN01 SPX CABFIN04...
Страница 29: ......
Страница 82: ...Appendix B Product Support LTPS UM 8007 01 Issue 1 70 November 9 2001 SPX CABFIN01 SPX CABFIN04...