The boiler is controlled by the MCBA (microprocessor), with the
control panel housed behind the front panel.

Standby Mode

Standby Mode is the normal operation display setting.

The first digit shows the boiler sequence. This sequence relates to
current boiler status. The last two digits show the boiler temperature.

If the burner is turned off because of an extra protection, the display
shows boiler-sequence 9 and the flow-temperature. This alternates
with the error code eg. b26

Sequence

0

1

2

3

4

5

6

7

8

9

A

G

H

L

t

Boiler status

Stand By, no heat request

Pre-purge, post-purge

Ignition

Burning in CH-mode

Burning in DHW-mode

Waiting for opening of Air pressure switch (max. 1 Min.)

Waiting for closing of Air pressure switch (max. 2 x 1 Min.)

Burner off because the set-value has been reached

Overrun time pump in CH-mode

Overrun time pump in DHW-mode

Burner off because of protection:

• “b08”: airflowsensor did not close

• “b18”: T1 > 95 °C

• “b19”: T2 > 95 °C

• “b24”: T2 - T1 > 10,20 or 40 °C after 19 minutes

• “b25”: dT1/dt > Maximum Gradient T1

• “b26”: Minimum gas or  water pressure switch not closed

• “b28”: no fan signal

• “b29”: fan signal, incorrect fan rotation

• “b30”: T1 - T2 > Max. delta

• “b33”: NTC3 short circuit

• “b35”: NTC5 short circuit

• “b38”: NTC3 open circuit

• “b40”: NTC5 open circuit

• “b52”: T5 > T5max

• “b61”: airflowsensor closed

• “b65”: wait for fanstart

Internal control

Burner on for holding boiler warm

Burner-high function: Testmode max. RPM in CH-mode

Burner-low function: Testmode min. RPM in CH-mode

Burner on for manual fanspeed (servicing)

Changing the MCBA settings: Parameter mode

Proceed as follows:
• 

Press the “MODE” button once; the display will show “PARA”.
Press the “STEP” button once; the first digit is “1” and the last
two show the setting for the first parameter.

• 

To change these last two, press “+” to increase and “-” to decrease.

• 

Save the new setting selected with the “STORE” button.

• 

To access the next parameter, press “STEP”.

• 

Press the “MODE” button twice to return to standby mode.

List of accessible parameters:

Temperature measurement display: Info mode

Proceed as follows:
• 

Press the “MODE” button twice; the display will show “INFO”.

• 

Press the “STEP” button once; the first digit is the measurement
number and the last two its value.

• 

Press the “STEP” button to display the next measurement.

• 

To return to standby mode, press the “MODE” button once.

List of measurements available:

Parameter N°

1

2

3

4

Range

20 - 90 °C

O = OFF; 1 = ON

O = OFF; 1 = ON

60 - 90 °C

Description

hot water setting

“Hot water” system status

“Heating” system status

Heating setting

Measurement N°

1

2

3

4

5

6

7

8

9

Description

Temperature T1 - primary

Temperature T2 - primary

Temperature T3 - secondary

Outside temperature T4

Flue gas temperature T5

Setting for T1

Variation of T1 - °C/s

Variation of T2 - °C/s

Variation of T3 - °C/s

Содержание Prestige 47

Страница 1: ...66400400 excellence in hot water Prestige 47 64 85 Installation Operating and Servicing Instructions...

Страница 2: ...h the prevailing standards ACV accepts no liability for any damage resulting from incorrect installation or from the use of components or fittings not specified by ACV Failure to observe instructions...

Страница 3: ...l heating situations For more information take contact with our local distributor MOUNTING BOILER The boiler should be installed in accordance with all the local and regional regulations 1 The boiler...

Страница 4: ...t by turning the white plastic screw on the gas valve clockwise higher CO2 counter clockwise lower CO2 In case the installation is supplied with a different type of gas the boiler has to be re adjuste...

Страница 5: ...n USING THE BOILER Your system should be serviced at least once a year by a qualified engineer If the boiler is subject to heavy use it may require servicing more than once a year consult your service...

Страница 6: ...b52 T5 T5max b61 airflowsensor closed b65 wait for fanstart Internal control Burner on for holding boiler warm Burner high function Testmode max RPM in CH mode Burner low function Testmode min RPM in...

Страница 7: ...sensor NTC2 check that the shunt pump is operating and if so vent the boiler if the fan is turning check the PWM connection if the problem persists after 2 resets change the fan if the problem persist...

Страница 8: ...e the burner hood Now the burner can be removed Inspect the fire chamber and the burner The burner can be cleaned with a nylon brush never use a steel brush on the inside so not on the side of the fla...

Отзывы: