6
TECHNICAL SPECIFICATION
MAXIMUM OPERATING CONDITIONS
Maximum service pressure
(tank full of water)
- Primary circuit: 3 bar
- Secondary circuit: 10 bar
Test pressure
(tank full of water)
- Primary circuit: 4.5 bar
- Secondary circuit: 13 bar
Operating temperature
- Maximum temperature: 90°C
Water quality
• Chlorures: < 150 mg/l (304)
< 2000 mg/l (Duplex)
• 6
≤
ph
≤
8
BURNER CHAMBER PLATE
The burner chamber plate secures the burner with 4 screw threads
(M 8). It is thermally insulated to protect it from the heat.
HM 200 N
HM 200 F
Peak delivery at 40°C
L/10’
1570
1675
Peak delivery at 45°C
L/10’
1350
1444
Peak delivery at 60°C
L/10’
915
961
Peak delivery at 70°C
L/10’
737
755
Peak delivery at 80°C
L/10’
586
586
Peak delivery at 40°C
L/60’
4920
5976
Peak delivery at 45°C
L/60’
4221
5131
Peak delivery at 60°C
L/60’
2925
3126
Peak delivery at 70°C
L/60’
2412
2309
Peak delivery at 80°C
L/60’
1712
1712
Continuous delivery at 40°C
L/h
4020
5161
Continuous delivery at 45°C
L/h’
3446
4424
Continuous delivery at 60°C
L/h’
2412
2598
Continuous delivery at 70°C
L/h’
2010
1864
Continuous delivery at 80°C
L/h’
1352
1352
N.B.:
The outputs above are given for a hot water temperature of 90°C and a cold water temperature of 10°C.
DOMESTIC HOT WATER PERFORMANCES
45°
Ø 130
Ø 170
Ø
22
Ø
46
4 x M8