8

INSTALLATION

HOT WATER CONNECTIONS

Pressure reducing valve

If the mains water pressure is greater than 6 bar, a pressure reducing
valve must be fitted.

Expansion relief valve

The tank expansion relief valve must be ACV approved and
calibrated to a maximum of 7 bar. The valve discharge must be
connected to the drain.

Hot water expansion vessel

We recommend installing a hot water expansion vessel.

Hot water circulation

If the tank is situated a long way from the point of use, then installing
a recirculation loop can provide a faster supply of hot water to the
outlets.

Temperature and pressure relief valve

If using the HeatMaster as an unvented hot water unit, in some
countries, a temperature and pressure relief valve must be fitted -
consult your ACV stockist for assistance.

Example of hot water connection with thermostatic
mixer

1.

Stop cock

2.

Non-return valve

3.

Pressure reducing valve

4.

Expansion relief valve

5.

Hot water expansion vessel

6.

Hot water secondary pump 

(it fitted)

7.

Thermostatic mixing valve

8.

Drawoff tap

9.

Drain cock

10. Stop cock for cleaning
11. Temperature relief valve 

(UK-only)

DANGER!
As a safety measure, we strongly advise
installing a thermostatic mixer to prevent the
risk of burns

Example of h storage connection

Recommended for applications requiring a high peak flow.

Example of series connection

Preferable for high temperature applications with up to three units.

Example of parallel connection

Recommended for applications with a high continuous flow.

1

2

3

4

5

2

6

7

8

9

10

11

I

O

I

O

I

O

I

O

I

O

I

O

I

O

D A N G E R

HOT

Содержание HeatMaster 200 F

Страница 1: ... 641 Primary circuit capacity L 241 241 Hot water connection Ø 2 2 Heating connection Ø 2 2 Chimney connection Ø mm 250 250 Water tank heat transfer surface m2 5 30 5 30 Drained weight Kg 530 550 Pressure loss of the primary circuit mbar 240 240 Combustion efficiency 93 5 93 7 Output CO2 12 8 12 9 Net temperature of the flue gases C 143 140 5 Mass flow rate of combustion products g sec 65 2 83 0 N...

Страница 2: ...L 10 1570 1675 Peak delivery at 45 C L 10 1350 1444 Peak delivery at 60 C L 10 915 961 Peak delivery at 70 C L 10 737 755 Peak delivery at 80 C L 10 586 586 Peak delivery at 40 C L 60 4920 5976 Peak delivery at 45 C L 60 4221 5131 Peak delivery at 60 C L 60 2925 3126 Peak delivery at 70 C L 60 2412 2309 Peak delivery at 80 C L 60 1712 1712 Continuous delivery at 40 C L h 4020 5161 Continuous deliv...

Страница 3: ...pical boiler connection B23 The boiler is connected to the chimney by a metal pipe rising at an angle from the boiler to the chimney A flue disconnection piece is required This must be easy to remove to give access to the flue pipes when servicing the boiler Ventilation 200 N 200 F Min fresh air requirement m3 h 277 353 Bottom dm2 2 45 2 45 Top dm2 4 62 5 88 Chimney minimum flue diameter 200 N 200...

Страница 4: ...ies a temperature and pressure relief valve must be fitted consult your ACV stockist for assistance Example of hot water connection with thermostatic mixer 1 Stop cock 2 Non return valve 3 Pressure reducing valve 4 Expansion relief valve 5 Hot water expansion vessel 6 Hot water secondary pump it fitted 7 Thermostatic mixing valve 8 Drawoff tap 9 Drain cock 10 Stop cock for cleaning 11 Temperature ...

Страница 5: ...Isolating valves 5 Safety valve set to 3 bar with pressure gauge 6 Expansion vessel 7 Drain cock 8 Controller optional 9 Surface mounted sensor optional WARNING The pimary safety valve is supplied with a plastic tube connected to the discharge outlet this is for test purposes only and should be removed The safety valve should be connected to a drain using a metallic pipe eg copper BEWARE In the ca...

Страница 6: ...circuit low water pressure indicator 6 Low water pressure switch 7 Time clock 8 Summer winter switch 9 Hot water priority link 10 Burner lockout indicator 11 Room thermostat connection option 12 Central heating pump 13 HeatMaster shunt pump 14 Burner plug connector 15 Water flow switch connection option 16 Thermal reset high limit thermostat 95 C 17 Control thermostat Electrical connection HeatMas...

Страница 7: ... them 6 Dismantle the chamber plate and remove the burner 7 Brush the flue ways 8 Clean the combustion chamber and the burner 9 Replace the turbulators the chimney reducer and the flue lining check that the seal on the chimney reducer is in good condition Replace the seal if necessary Horizontal flue gas outlet reducer 3 Loosen the nuts and remove the chimney reducer 5 Take out the turbulators fro...

Страница 8: ... 4 Open valve 9 then valve 10 5 Let the water empty into the drain For the tank to be emptied valve 9 must be situated at ground level D A N G E R HOT 1 2 3 4 5 2 6 7 8 9 10 11 I O 1 4 2 3 6 5 8 I O 7 4 9 PLACING THE BURNER IN SAFETY MODE When the burner is in safety mode the safety indicator located on the burner and the control panel lights up The red warning light indicates an operating fault W...

Отзывы: