E
N
FR
R
U
P
L
DE
IT
ES
N
L
EN • 17
664Y5400•B
INSTALLATION
HEATING CONNECTION
The DHW tank must be pressurized before putting the
primary circuit (heating) under pressure.
Two couplings are installed at the back of the HeatMaster®, that can be
used to connect a central heating circuit.
Connecting a heating system may reduce the domestic hot water
performance.
EXPANSION VESSEL
The HeatMaster® 30 N and 60 N are fitted with an 8 liter expansion
vessel.
The HeatMaster® 70 N and 100 N are fitted with two 10 liter expansion
vessels. These expansion vessels are sized for hot water operation only.
If the heating system is connected to the primary circuit, calculate
the expansion capacity necessary for the total volume of the heating
system (refer to the technical instructions from a relevant manufacturer
of expansion vessels).
WARNING
The primary safety valve is supplied with a plastic tube
connected to discharge outlet - this is for test purposes
only and should be removed.
The safety valve should be connected to the sewer using a
metallic pipe, e.g. copper.
1. 4-way mixing valve
2. Heating pump
3. Check valve
4. Heating circuit isolating valves
5. Safety valve set at 3 bar with pressure gauge
6. Expansion vessel
7. Drain valve
8. Primary circuit filling valve
9. Controller
10. Contact sensor
11. Room thermostat
12. Outdoor temperature sensor
1
7
8
4
4
2
5
I
O
6
6
3
10
9
12
11
Содержание HeatMaster 100 N
Страница 16: ...EN FR RU PL DE IT ES NL EN 15 664Y5400 B INSTALLATION 2 x 1 2 3 4 5 6...
Страница 21: ...EN FR RU PL DE IT ES NL EN 20 664Y5400 B...
Страница 22: ...EN FR RU PL DE IT ES NL EN 21 664Y5400 B...
Страница 23: ...EN FR RU PL DE IT ES NL EN 22 664Y5400 B...
Страница 24: ...EN FR RU PL DE IT ES NL EN 23 664Y5400 B...
Страница 25: ......
Страница 26: ......
Страница 27: ......