INSTALLATION

DHW CONNECTION

  The DHW tank must be pressurized before putting the 

primary circuit (heating) under pressure.

The HeatMaster® boiler can be connected directly to the DHW circuit.

Flush the system before connecting the domestic hot water circuit.

The installation must be fitted with an approved safety group, comprised 

of a 7 bar safety valve, a check valve and a shut-off valve.

During the heating process, the domestic hot water expands and the 

pressure increases. As soon as the pressure exceeds the safety valve 

setting, the valve opens and discharges a small quantity of water. 

Using a hot water expansion vessel (2 liters at least) will prevent this 

phenomenon and reduce the water hammer effect.

  The hot water output may reach temperatures in excess of 

60°C, which can cause burns.

 

ACV therefore recommends that you install a thermostatic 

mixing valve immediately after the appliance outlet.

  If stop valves are used in the domestic hot water system, 

they can cause pressure changes when closed.

 

Use devices designed to reduce water hammer effect to 

avoid this phenomenon.

  1.  Cold water supply valve

 2.  Check valve

  3.  Pressure reducing valve

  4.  Domestic hot water safety valve set at 7 bar

  5.  DHW circuit expansion vessel

 6.  DHW secondary pump (if fitted)

  7.  Thermostatic mixing valve

 8.  Draw-off tap

  9.  Draining valve

 10.  Stop valve for cleaning

 11.  Temperature relief valve (UK only)

1 2

3

4

5

2

6

7

8

9

10

11

I

O

EXAMPLE OF H STORAGE CONNECTION

Recommended for applications requiring a high peak flow.

I

O

EXAMPLE OF PARALLEL CONNECTION

Recommended for applications with a high constant flow.

I

O

I

O

I

O

EXAMPLE OF SERIES CONNECTION

Preferable for high-temperature applications with up to 3 units

I

O

I

O

I

O

Содержание HeatMaster 100 N

Страница 1: ...EN FR RU PL DE IT ES NL EN 1 664Y5400 B INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS HeatMaster 30 N 60 N 70 N 100 N...

Страница 2: ...E ES IT PL RU M M L1 N PE P t t t 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 P 1 2 C 2 1 3 1 5 4 2 t C 2 1 t C 2 1 3 2 1 5 11 10 12 13 9 15 16 14 8 7 6 4 Br B Br Br O G B B B B B B B B B Y Gr...

Страница 3: ...ctrical Characteristics 13 INSTALLATION 14 Package Contents 14 Boiler Preparation 14 DHW Connection 16 Heating Connection 17 STARTING UP 18 Filling the DHW and Heating Circuits 18 Starting up the Boil...

Страница 4: ...s and features of its products without prior notice The availability of certain models as well as their accessories may vary according to markets WARNINGS RECOMMENDATIONS Please carefully read this ma...

Страница 5: ...pencil or similar pointed device then reinstall the cap If the fault persists turn the boiler off and call a service engineer Daily timer Allows the HeatMaster to be turned on and off at specific mome...

Страница 6: ...g valve Safety valves If water discharges from any of the safety valves turn the boiler off and call a service engineer BURNER SAFETY MECHANISM SAFETY CUTOUT OF THE OIL OR GAS BURNER HeatMaster 30 N T...

Страница 7: ...Heating circuit outlet 14 Domestic hot water outlet 15 Stainless steel Tank in Tank hot water production tank 16 Flue pipes and turbulators 17 Primary circuit 18 Heating circuit return 19 Combustion c...

Страница 8: ...tlet 14 Domestic hot water outlet 15 Stainless steel Tank in Tank hot water production tank 16 Flue pipes and turbulators 17 Primary circuit 18 Heating circuit return 19 Combustion chamber 20 Oil burn...

Страница 9: ...390 1619 1382 284 126 HeatMaster 30 N 60 N 310 340 680 1728 HM 70 N 2128 HM 100 N 1743 HM 70 N 2093 HM 100 N 340 342 428 831 678 390 1613 HM 100 N 285 127 1641 HM 70 N 2045 HM 100 N HeatMaster 70 N 10...

Страница 10: ...d Minimum A mm 650 500 B mm 800 700 C mm 500 300 D mm 300 250 E mm 150 100 F mm 800 700 C A B D C A B E F C B C A B E F E F BURNER CHAMBER PLATE The burner chamber plate has four threaded holes M8 to...

Страница 11: ...nection F 1 1 2 1 1 2 1 1 2 1 1 2 DHW Connection M 3 4 3 4 1 1 DHW tank heat exchanger surface m2 2 46 2 46 3 14 3 95 Primary circuit water pressure drop T 20K mbar 27 54 46 83 Total capacity L 162 16...

Страница 12: ...Minimum supply of fresh air into the boiler room Fresh air supply High Low B23 and B23P HeatMaster 30N cm2 150 200 HeatMaster 60N cm2 150 200 HeatMaster 70 N cm2 150 200 HeatMaster 100N cm2 210 320 D...

Страница 13: ...150 1m straight pipe 6 1 6 2 90 elbow 15 2 15 5 45 elbow 6 1 6 2 Condensate recovery container _ 2 _ 4 Terminal 20 10 20 20 This table is based on ACV equipment and cannot be applied as a rule In the...

Страница 14: ...high limit thermostat 5 Low primary water pressure indicator 6 Low water pressure switch 7 Daily timer 8 Summer winter switch 9 Burner safety cutout warning indicator 10 Room temperature option 11 He...

Страница 15: ...wrapped in a plastic film At product reception and after removal of packaging check the package contents and that the appliance is free of damages Contents A HeatMaster N boiler Installation operation...

Страница 16: ...EN FR RU PL DE IT ES NL EN 15 664Y5400 B INSTALLATION 2 x 1 2 3 4 5 6...

Страница 17: ...peratures in excess of 60 C which can cause burns ACV therefore recommends that you install a thermostatic mixing valve immediately after the appliance outlet If stop valves are used in the domestic h...

Страница 18: ...ly If the heating system is connected to the primary circuit calculate the expansion capacity necessary for the total volume of the heating system refer to the technical instructions from a relevant m...

Страница 19: ...ntil you reach an approximate pressure of 1 5 bar in the system 4 Bleed the boiler and the whole system using the automatic air bleed valve located on top of the appliance STARTING UP THE BOILER START...

Страница 20: ...devices are working properly Test the safety valves on the central heating and hot water circuits SERVICING THE BURNER Forallburners pleaserefertotherelevantservicingandtroubleshooting instructions i...

Страница 21: ...EN FR RU PL DE IT ES NL EN 20 664Y5400 B...

Страница 22: ...EN FR RU PL DE IT ES NL EN 21 664Y5400 B...

Страница 23: ...EN FR RU PL DE IT ES NL EN 22 664Y5400 B...

Страница 24: ...EN FR RU PL DE IT ES NL EN 23 664Y5400 B...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Отзывы: