36
Installer's Handbook (Evo) - 660Y3000 • A
EN
PUMPS (HEATMASTER 25C & 25-35-45-70-85-120TC EVO)
The pump configurator system is based on the demands of the hydraulic system that you design. In
the table below, you will find the 4 configurations that have been preset in the ACVMax controller
for the HeatMaster 25C Evo and HeatMaster 25-35-45-70-85-120 TC Evo, based on different
hydraulic schemes that can be used.
The table shows which relays are activated under which condition.
The names in the table refer to the demand done by CH1 by CH2 or DHW respectively, the demand
to open/close the Motor of a mixing valve or reflect the activation of the alarm (error) or Flame output
relay.
In the following pages, you will find diagrams for HeatMaster C and TC, with a configuration number
that corresponds to the setting in the display.
Con-
fig. No
Flex 4
ERR
Flex 6
P4
Flex 3
P3
Flex 2
DHW
Flex 1
CH
Flex 5
FL
5
Error/Flame
CH2
CH1
DHW
CH1/CH2/
DHW
Flame
14
Error/Flame
Mix open
CH1/CH2
CH1
CH1/CH2/
DHW
Mix close
15
Mix open
CH2
CH1/CH2
CH1
CH1/CH2/
DHW
Mix close
16
Error/Flame
CH2
CH1/CH2
CH1
CH1/CH2/
DHW
Flame
RESISTANCE OF THE TEMPERATURE SENSORS
T° [°C]
R Ω
T° [°C]
R Ω
T° [°C]
R Ω
- 20
98200
25
12000
70
2340
- 15
75900
30
9800
75
1940
- 10
58800
35
8050
80
1710
- 5
45900
40
6650
85
1470
0
36100
45
5520
90
1260
5
28600
50
4610
95
1100
10
22800
55
3860
100
950
15
18300
60
3250
20
14700
65
2750