21
Installer's Handbook (Evo) - 660Y3000 • A
EN
Boiler Settings
Boiler Settings
Model HeatMaster
Lockout Temp.
221°F [105°C]
Modbus Address
0=BCST
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
Pump Settings
Current Pump Config
Config 16
Preset Pump Config
Flexible Pump Config
Pump PWM minimum
100%
Flexible Pump Config
Flex. Relay 1
Flex. Relay 2
Flex. Relay 3
Flex. Relay 4
Flex. Relay 5
Flex. Relay 6
Flex. Relay 1
CH1 On
CH2
On
DHW On
MIX OPEN Off
MIX CLOSE
Off
ERROR Off
FLAME Off
Each relay function has several options. Activation will happen when one of the following options has been chosen:
CH1, CH2, DHW, MIX OPEN, MIX CLOSE, ERROR, FLAME.
More than one action can be chosen for one relay (one relay can become active for CH1 , CH2 and DHW demand when needed.)
Touch the
UP
or
DOWN
soft keys to scroll through the settings, then
OK
to toggle between the On/Off status of
each relay. Then go to the next line, until you reach the last line.
•
When selecting
CH1
, the relay is activated at CH1 demand.
•
When selecting
CH2
, the relay is activated at CH2 demand.
•
When selecting
DHW
, the relay is activated at DHW demand.
•
When selecting
Mix Open
, the Mixing valve open input is activated. Provided there is a mixing valve in the hy-
draulic circuit, runtime is assumed to be 120 sec.
•
When selecting
Mix Close
, the Mixing valve close input is activated. Provided there is a mixing valve in the hy-
draulic circuit, runtime is assumed to be 120 sec.
•
When selecting
ERROR
, the relay is activated on error.
•
When selecting
FLAME
, the relay is activated when appliance is running and a flame signal has been detected.
Touch
OK
to activate
Save & Exit
. This will ensure that the changed data are stored in the appliance.
Flex. Relay 1
CH2 Off
DHW Off
MIX OPEN Off
MIX CLOSE
Off
ERROR Off
FLAME Off
Save & Exit
By touching the
RIGHT
key then
OK,
you go back to the previous screen, but THE CHANGED VALUES ARE
NOT STORED in the memory (Quick escape route).
To save your changes, make sure to scroll down to the last line of the screen and to select
Save & Exit
.
Then touch
OK
to activate the function.
There are three possible selections to activate the
Error Relay
(alarm) contact:
• On Lockout, Blocking and Warning
: the error relay is activated at a non-volatile lock-out (e.g. CH Flow NTC defect), at a
blocking error (self-resetting errors) (e.g. Gas-pressure switch not closed ), or at a warning (e.g. low water pressure warning).
• On Lock-out and blocking
: the error relay is activated at a non-volatile lock-out or a blocking error.
• On Lockout
: the error relay is activated at a non-volatile lock-out only.
The selection depends on the alarm feedback requirement from the customer.
Flexible Pump Config
Flex. Relay 2
Flex. Relay 3
Flex. Relay 4
Flex. Relay 5
Flex. Relay 6
Error Relay
Error Relay
On Lockout, Blocking and Warning
On Lockout and Blocking
On Lockout
DESCRIPTION AND OPERATION