22
Installer's Handbook (Evo) - 660Y3000 • A
EN
The
Ignition Level
parameter allows to change the fan start speed of the appliance.
Touch the
LEFT
or
RIGHT
soft keys to adjust the settings, then
OK
to validate your selection.
Default
: See table below for the fan speed applicable to each appliance/gas combination
Boiler Settings
Boiler Settings
Model HeatMaster
Lockout Temp.
221°F [105°C]
Modbus Address
0=BCST
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
Pump Settings
Current Pump Config
Config 16
Preset Pump Config
Flexible Pump Config
Pump PWM minimum
100%
Boiler Settings
Model HeatMaster
Lockout Temp.
221°F [105°C]
Modbus Address
0=BCST
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
Ignition Level
3750rpm
1400rpm
5200rpm
Pump PWM minimum
100%
1%
100%
Natural Gas (G20)
Propane (G31)
HeatMaster / WaterMaster Evo
25 kW
3750 rpm
3750 rpm
35 kW
3750 rpm
3750 rpm
45 kW
3750 rpm
3750 rpm
70 kW
3750 rpm
3750 rpm
85 kW
3750 rpm
3750 rpm
120 kW
4300 rpm
4300 rpm
The
Pump PWM minimum
function allows to adjust the minimum pump setting if the flow in the appli-
ance / system is insufficient at minimum appliance rate.
Touch the
LEFT
or
RIGHT
soft keys to increase/decrease the value, then
OK
to validate your selection.
Default: 100%
Mix zone high limit
45°C
20°C
80°C
Boiler Settings
Prestige Model
HeatMaster
Lockout Temp.
221°F [105°C]
Modbus Address
0=BCST
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
The
Mix zone high limit
setting allows to limit the maximum temperature in the mixed circuit. The function works like an Overheat Cut-
off Activation of the limit and will cause the appliance to go in fault state (lockout). This setting allows to change the limit temperature
for the mixed circuit. It is based on the CH1 setpoint.
Be aware that for Floor Heating systems this temperature may NOT be adjusted. A higher temperature setting may
damage your floor heating circuit
Touch the
LEFT
or
RIGHT
soft keys to decrease/increase the temperature value, then
OK
to validate your selection.
Default: 45°C
DESCRIPTION AND OPERATION