ALARM MATRIX
Description
Type Alarm Condition
Reset Condition
Discharge Temperature 1 /
High Pressure Comp 1 Fault
Alarm
Temperature out of Range
Temperature &
Pressure Normal
Compressor 1 High Pressure
Discharge Temperature 2 /
High Pressure Comp 2 Fault
Alarm
Temperature out of Range
Temperature &
Pressure Normal
Compressor 2 High Pressure
Compressor 1 LP Fault
Alarm
Compressor 1 Low Pressure
Normal Pressure
Compressor 2 LP Fault
Alarm
Compressor 2 Low Pressure
Normal Pressure
Outdoor Coil Temp1 Fault
Warning Temperature out of Range
Temperature OK
Outdoor Coil Temp2 Fault
Warning Temperature out of Range
Temperature OK
Room Air Temperature
Sensor Fault
Warning Temperature out of Range
Temperature OK
Outside Air Temperature
Sensor Fault
Warning Temperature out of Range
Temperature OK
Filter Alarm
Alarm
Air Filter Timer Timed-Out
Clean / Replace Filter
and Reset Timer
Anti-Freeze Protection
Warning
Indoor Coil
Temperature Too Low
Normal Operating
Temperature
Indoor Coil Sensor Fault
Warning Temperature out of Range
Temperature OK
IMPORTANT NOTE
:
All alarm fault conditions must be investigated and rectified before proceeding to reset or
clear the alarm. If the cause of the fault condition has not been eliminated, the alarm fault
conditions will be reported and logged in again on next data cycle.
Repeated resetting and
restarting can cause damage to the unit and may render your warranty null & void.