Installation and Commissioning Guide
Split Tri-Capacity
7
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
04. INSTALLATION INFORMATION
All service technicians handling refrigerant must be licensed to handle refrigerant gases.
Recover and Recycle Refrigerants
Never release refrigerant to the atmosphere! It is an offence in Australia to do so. Always recover, recycle and reuse
refrigerants. When removing from the system, properly contain and identify refrigerants in its dedicated container for
proper disposal and/or storage. Always consider the recycle or reclaim requirements of the refrigerant before beginning the
recovery procedures. Obtain a chemical analysis of the refrigerant if necessary. Refer recovered refrigerant and acceptable
refrigerant quality to existing standards and regulations.
Refrigerant Handling and Safety
Consult the refrigerant manufacturer’s Material Safety Data Sheet (MSDS) for information on proper handling and to
fully understand health, safety, storage and disposal requirements. Use the approved containment vessels and refer to
appropriate safety standards. Comply with all applicable transportation standards when shipping refrigerant containers.
Service Equipment and Recovery Procedures
Always use refrigerant reclaiming equipment in order to minimise refrigerant emissions. Use equipment and methods which
will pull the lowest possible system vacuum while recovering and condensing refrigerant. Equipment capable of pulling a
vacuum of less than 500 microns is required.
Do not open the system to the atmosphere for service work until refrigerant is fully removed and/or recovered. Perform
refrigeration system evacuation, prior to charging, in accordance with AIRAH / IRHACE Refrigerant handling code of
practice.
Let the unit stand for 1 hour and with the vacuum not rising above 500 microns. A rise above 500 microns indicates a leak
from the system and a leak test is required to locate and repair any leak.
CAUTION
A leak test is always required on any repaired section of the refrigeration system.
Charge refrigerant into the system only after the equipment does not leak or contain moisture. Ensure that R-410A is only
charged in liquid form. Take into consideration the correct amount of refrigerant charge specified for the system to ensure
efficient unit operations. When charging is complete, reclaim refrigerant from charging lines into an approved refrigerant
container. Seal all used refrigerant containers with approved closure devices to prevent unused refrigerant from escaping
to the atmosphere. Take extra care to maintain all service equipment directly supporting refrigerant service work such as
gauges, hoses, vacuum pumps and recycling equipment.