Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
Installation and Commissioning Guide
Split Tri-Capacity
07. OUTDOOR DIMENSIONS
07.01. CAY500T Unit Dimension
Unit Model
Number
Unit
Weight
Corner Weights(kg)
Centre Of
Gravity Position
A
B
C
D
E
F
XX
YY
CAY500T
542
64
61
113
88
88
128
931
569
150
40
75
102
1465
O/A
375
50
375
97
770
(MTG C-C DIST)
175
1266
XX
YY
2305 O/A
460
670
605
415
375
1195
O/A
30
30
ALL 50
SMALL GAS
Ø 22.2 (7/8")
OU
TD
OO
R
C
O
IL
OUTDOOR COIL
OUTDOOR COIL
CONDENSATE
DRAIN
25.4 (1")
BSP SOCKET
P
DETAIL P
SMALL LIQ
Ø 9.5 (3/8")
LARGE GAS
Ø 28.6 (1-1/8")
LARGE LIQ
Ø 15.9 (5/8")
6 x Ø 20.0
MTG. HOLES
770
(MTG C-C DIST)
1135
(MTG C-C DIST)
TOP VIEW
OVERALL NOMINAL DIMENSION (H X W X D)
= 1465 X 2305 X 1195
THIRD ANGLE
PROJECTION
SIDE VIEW
FRONT VIEW
NOTES:
1. Do not scale drawing. All dimensions are in mm unless specified. Refer to
corresponding unit dimensional drawing for mounting hole details.
2. Service Access Areas and Spaces for Airflow Clearances given are
suggested minimum based on the condition that the spaces around the
units are free from any obstructions and a walkway passage of 1000mm
between the units or between the unit and the outside perimeter is
available.
3. Minimum service access areas and spaces for airflow clearances are
responsibilities of the installer, ActronAir will not be held liable for any
extra charges incurred due to lack of access and space for airflow.
4. Under all circumstances, condenser air must not recirculate back onto
condenser coil. Keep all clearance free of any obstructions.
5. Maximum External Static of Outdoor Fans is 20 Pa.
6. STACKING OF UNITS: Ensure that minimum airflow and clearances are met.
7. Refer to Pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9. Use M12 bolt for feet mounting.
HEIGHT CLEARANCE = 1500
TOP VIEW
D
B
C
A
F
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
SERVICE ACCESS AREAS
1000 mm
SERVICE
CLEARANCE
(COMPRESSOR
and
ELECTRICALS)
YY
XX
500 mm
AIRFLOW ALLOWANCE
500 mm
AIRFL
O
W ALL
O
W
ANCE
300 mm
SPACE CLEARANCE
E
DETAIL P