56
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
Installation and Commissioning Guide
Split Tri-Capacity
Option 2: TIME SCHEDULER
Ensure that
Enable DIN 4 to turn the unit On / Off
(on screen
Ge3
) is set to
NO
.
NO
Bms Config. Ge3
Enable DIN 4 to turn
the unit On / Off : NO
Ensure
Enable Scheduler
(on screen
D1
) must be
Yes
.
Clock D1
YES
Day : Tuesday
Date : 17/05/16
Hour : 12:38
Enable Scheduler : YES
Then set the weekly, After Hours and special days time scheduler via screens (
D3
–
D19
) to your requirements.
The Unit ON/OFF is now configured.
Unit ON/OFF CP05
(CP10, CL01 optional)
SCHEDULE
UNIT STATUS
ON
ON
Unit On
ON
OFF
OFF by SCH
OFF
ON or OFF
OFF by KEY
Option 3: External Unit ON/OFF
The Unit ON/OFF can be controlled via external relay
Unit ON/OFF CP05
(CP10, CL01 optional)
REMOTE ON/OFF
UNIT STATUS
ON
ON
Unit On
ON
OFF
OFF by DIN
OFF
ON or OFF
OFF by KEY
19.01.01. Wiring ON/OFF Input
Unit ON/OFF can be wired using either
Method 1: External Unit ON/OFF
or
Method 2: IN-FAN (24VAC IN)
.
Method 1: External Unit ON/OFF
External Unit ON/OFF is operated by switching REMOTE ON/OFF to COMMON.
COMMON (GND)
11
REMOTE ON/OFF
10
TERMINALS