18. EXTERNAL INPUT OPERATION
The System is controlled by Third Party Control through wired inputs.
(On/Off, Indoor Fan, Compressor, Heat/Cool and Economy)
REMOTE ON/OFF can only be used when
Enable Scheduler
is set to
NO
(on screen
D1
).
18.01. Unit ON/OFF Configuration.
The unit ON/OFF can be configured as follows:
18.01.01. Wiring ON/OFF Input
Unit ON/OFF can be wired using either Method 1 (REMOTE ON/OFF) or Method 2 ( IN-FAN (24VAC IN)) as
shown below:
Method 1:
Unit ON/OFF is configured by switching
REMOTE ON/OFF
to
COMMON
.
COMMON (GND)
11
REMOTE ON/OFF
10
TERMINALS
Method 2:
IN-FAN is operated by switching 24VAC. The unit will turn On or Off when the switch is closed or open
respectively.
IN-FAN (24VAC IN)
6
24VAC OUT
1
TERMINALS
18.01.02. Setting ON/OFF Input
Set
Enable DIN 4 to turn the unit On / Off
(on screen
Ge3
) to
Yes
.
Yes
Bms Config. Ge3
Enable DIN 4 to turn
the unit On / Off : Yes
The Unit ON/OFF is now configured.
18.02. EC Indoor Fan Commissioning
Unit control mode is set to
EXTERNAL INPUT
via
Gfc11
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
EXTERNAL INPUT
S. Configuration Gfc11
Unit control mode :
EXTERNAL INPUT
Supply Fan Control :
Select Wall Control :
SINGLE CL01