Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Troubleshooting Guide
Advance Split Ducted Unit
01. General Troubleshooting
Fault
Possible Causes
Remedies
The system does not start.
Built-in safety timers have been activated.
Allow up to 5 minutes for the system to start
from when it is turned on.
A circuit breaker may have tripped.
Check circuit breakers.
The thermostat setpoint is incorrect.
Lower the set point on cooling or raise it on
heating modes.
The master wall control timer is set.
Check the wall control timer settings.
No airflow from the outlets.
During heating operation, the hot start function
may have been activated.
During heating operation, the indoor fan is
delayed for 30 seconds or until the indoor coil
reaches 25
o
C (whichever occur first). This is to
prevent cold drafts.
The system may be operating in a defrost
cycle during the heating cycle. (LR7 will display
DEFROST.
NEO will display
Defrosting.
)
This is normal operation during the defrost
cycle to prevent cold air being blown into
rooms.
Cooling/Heating is not sufficient.
The return air filter may be dirty.
Clean the return air filter.
The outdoor unit may have an obstruction on
the air inlet or outlet.
Ensure the air inlet and air outlet on the
outdoor unit is not blocked.
Check that the area around the outdoor unit
is free from obstructions that may cause the
airflow to recirculate.
The airflow across the indoor coil may be
outside of the operating range.
Reduce the total static pressure of the
ductwork. For example increase duct sizes,
reduce tight duct work bends or increase
return air grille size.
The heat load is greater than the installation
design.
Perform a heat load analysis on the
conditioned space. Turn any unused zones to
the off position.
Windows or doors are open.
Close windows and doors in conditioned areas.
The outside temperature is beyond the air
conditioner design conditions.
When the ambient temperature is expected
to exceed the maximum design operating
temperature, turn the system on as early as
possible.
The indoor fan setting may be set too low.
Change the fan speed to a higher setting. This
will increase system capacity.
Steam emitted from outdoor unit.
The outdoor unit is going through a defrost
cycle during the heating cycle.
This is normal during the defrost operation in
cold ambient conditions.
Condensation of water on the outdoor coil
during heating operation.
This is normal during heating operation.
Optional drip trays can be purchased to drain
the excess water.
Set temperature cannot be
adjusted.
The wall control set temperature limits are being
exceeded.
Check the upper and lower temperature limits
are set correctly.
Occasional hissing noise can be
heard during the heating cycle.
This is the sound of the gas changing direction
as the system goes through a defrost cycle.
This is a normal function of an air conditioner.
The compressor is operating but
the system is not cooling.
You are in heating mode.
Check the temperature settings.
The reversing valve has not switched between
heating and cooling.
Test reversing valve.