13
Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Troubleshooting Guide
Advance Split Ducted Unit
04.07. Other Component Coil Resistances
Component Name
Resistance Value (KΩ)*
Reversing valve
2.03
Crankcase Heater
1.56
*Resistance value at 25
o
C Ambient Temperature
04.08. EEV Resistance
Resistance Between Wires
Resistance Value (Ω)*
Orange – Grey
46 ± 3 Ω
Red – Grey
46 ± 3 Ω
Yellow – Grey
46 ± 3 Ω
Black – Grey
46 ± 3 Ω
*Resistance value at 20
o
C Ambient Temperature
04.09. Temperature-Resistance Table For Sensors
Ambient/Outdoor Coil/
Indoor Coil/Suction
Temperature Sensor
Discharge Line
Temperature Sensor
Temp
(°C)
Resistance
(KΩ)
Resistance
(KΩ)
-20
77.5
1053.9
-19
73.5
992.1
-18
69.7
933.0
-17
66.1
878.0
-16
62.8
827.0
-15
59.6
779.6
-14
56.6
734.7
-13
53.8
693.2
-12
51.2
654.0
-11
48.7
617.1
-10
46.3
582.5
-9
44.1
550.6
-8
42.0
520.2
-7
40.0
491.8
-6
38.1
465.2
-5
36.3
440.4
-4
34.6
416.9
-3
33.0
394.8
-2
31.5
374.1