14
Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Troubleshooting Guide
Advance Split Ducted Unit
Ambient/Outdoor Coil/
Indoor Coil/Suction
Temperature Sensor
Discharge Line
Temperature Sensor
Temp
(°C)
Resistance
(KΩ)
Resistance
(KΩ)
-1
30.1
354.7
0
28.7
336.4
1
27.4
319.0
2
26.2
302.7
3
25.0
287.3
4
23.9
273.0
5
22.9
259.2
6
21.9
246.4
7
21.0
234.3
8
20.1
222.8
9
19.2
212.0
10
18.4
201.8
11
17.6
192.1
12
16.9
183.0
13
16.2
174.3
14
15.5
166.1
15
14.9
158.4
16
14.3
151.1
17
13.7
144.1
18
13.2
137.5
19
12.7
131.3
20
12.2
125.4
21
11.7
119.7
22
11.2
114.4
23
10.8
109.4
24
10.4
104.6
25
10.0
100.0
26
9.6
95.7
27
9.3
91.6
28
8.9
87.6
29
8.6
83.9
30
8.3
80.4
31
8.0
77.0
32
7.7
73.8
33
7.4
70.7
34
7.1
67.8
35
6.9
65.1