15
Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Troubleshooting Guide
Advance Split Ducted Unit
Ambient/Outdoor Coil/
Indoor Coil/Suction
Temperature Sensor
Discharge Line
Temperature Sensor
Temp
(°C)
Resistance
(KΩ)
Resistance
(KΩ)
36
6.6
62.4
37
6.4
59.9
38
6.2
57.5
39
6.0
55.2
40
5.8
53.0
41
5.6
50.9
42
5.4
48.9
43
5.2
47.0
44
5.0
45.2
45
4.8
43.5
46
4.7
41.8
47
4.5
40.2
48
4.4
38.7
49
4.2
37.3
50
4.1
35.9
51
4.0
34.6
52
3.8
33.3
53
3.7
32.1
54
3.6
30.9
55
3.5
29.8
56
3.4
28.7
57
3.3
27.7
58
3.2
26.7
59
3.1
25.8
60
3.0
24.9
61
2.9
24.0
62
2.8
23.2
63
2.7
22.4
64
2.6
21.6
65
2.6
20.9
66
2.5
20.2
67
2.4
19.5
68
2.3
18.8
69
2.3
18.2
70
2.2
17.6
71
2.1
17.0
72
2.1
16.5
73
2.0
15.9
74
2.0
15.4
75
1.9
14.9
76
1.9
14.4