INSTALLATION REQUIREMENTS
• This unit must be installed by a licensed HVAC contractor or
electrician; failure to do so will void warranty of the product
• When the unit is installed in a roof mounted HVAC system, the unit
must be protected from the elements
If installed near a furnace or where emergency heat coils could raise
the temperature inside the plenum, cycle the AC unit through three full
heating cycles assuring that the temperature never exceeds 200
°
F
(93
°
C). The ActivePure
®
Cell must not exceed 200
°
F (93
°
C).
WARNING
For 120V Domestic Units: Black
= L1, White = Neutral, Green = Ground
For 220V Commercial Units: Black
= L1, White = L2, Green = Ground
For 230V International Units: Brown
= L1, Blue = L2, Green w/yellow stripe = Ground
ELECTRICAL REQUIREMENTS
• Wiring of the unit into your HVAC system should be done by a
licensed HVAC installer or electrical contractor only
• This unit is equipped with a universal ballast that operates at
nominal voltages between 100 and 240 VAC, 50/60 Hz
CAUTION
To Reduce the Risk of Electric Shock – DO NOT use in wet or damp
locations. This equipment emits UV-C radiation. DO NOT locate
equipment in any location allowing direct line-of-sight to vents,
returns, or other duct openings. Disconnect from supply before
servicing or replacing.
WARNING
1 . The ActivePure
®
Induct Guardian unit should be installed
after the air handler in the HVAC system .
2 . The ductwork around the installation area should be clean
and dry to ensure proper adhesion of the gasket materials
and any tape used .
3 . When installing near a furnace or heating coils, run the
heating system through three (3) full heating cycles to
ensure the temperature of the INDUCT unit does not
exceed 200 ˚F (93
°
C) .
4 . An approximate 3 .5” (8 .89 cm) opening will need to be cut
into the existing ductwork to install the unit properly .
5 . After a few minutes, adjust the control to the desired speed .
Min . 8” x 8”
Air Handler
Max .
6 ft .
NOTE:
Unit requires power 24/7 . Do not install where power to the unit will be cycled on and off .
Installation Clearance
CAUTION