background image

BLACK

GREEN/

YELLOW

BROWN

BLUE

ELECTRICAL THERMAL RELEASE

(SPRING BIASED TEST SWITCH)

ELECTRICAL THERMAL RELEASE

(SPRING BIASED TEST SWITCH)

TF 72 

°

C

TF 72 

°

C

2

1

S2

S3

S4

S5

S6

S1

N

E

M

L

VOLT FREE CONTACT
CHANGES OVER WHEN
DAMPER RELEASED 
RATED 24V 3A

VOLT FREE CONTACT
CHANGES OVER WHEN
DAMPER RESET 
RATED 24V 3A

SUPPLY
24V A.C. OR D.C.  
TYPICALLY 7W (MOTORING) 2W (RESET)

COMMON

NORMALLY CLOSED

NORMALLY OPEN

NORMALLY CLOSED

NORMALLY OPEN

COMMON

VOLT FREE CONTACT
CHANGES OVER WHEN
DAMPER RESET 
RATED 240V 2A

COMMON

NORMALLY CLOSED

NORMALLY OPEN

2

1

S2

S3

S4

S5

S6

S1

N

M

L

VOLT FREE CONTACT
CHANGES OVER WHEN
DAMPER RELEASED 
RATED 240V 3A

VOLT FREE CONTACT
CHANGES OVER WHEN
DAMPER RESET 
RATED 240V 3A

SUPPLY
220 - 240V A.C. 50/60Hz
TYPICALLY 8W (MOTORING) 3W (RESET)

COMMON

NORMALLY CLOSED

NORMALLY OPEN

NORMALLY CLOSED

NORMALLY OPEN

COMMON

5

Smoke/Shield PTC™        Vent/Shield PTC™

Smoke/Shield PTC
Application and
Wiring

Mode 1 

(Manual System)

Manual opening.
Spring instant closure via mechanical
fusible link.

(Smoke/Shield version only, Vent/Shield not available.)

Mode 5

(24V System)

Power On – Damper motors open.
Power Off – Spring closure or via
Electrical Thermal Release.

External mechanical position indicator
with pointer.
Release Time 

16 secs.

Reset Time 

≈ 

140 secs.

(Connect 24V via a safety isolating transformer.)

Vent/Shield PTC™ dampers and
associated control modes 5 and 6
are reverse acting with spring action
opening.

Mode 6

(230V System)

Power On – Damper motors open.
Power Off – Spring closure or via
Electrical Thermal Release.

External mechanical position indicator
with pointer.
Release Time 

16 secs.

Reset Time 

≈ 

1c secs.

(To isolate from main power supply, the system must
incorporate a device which disconnects the phase
conductors, with a least 3mm contact gap.)

General

One metre of halogen free low smoke
and fume electric cable is also
included with each control mode for
convenience of on site wiring. This
also provides the distinct safety
advantage of all electrics terminating
outside the duct, eliminating potential
in-duct fire hazards from wiring faults. 

The Electrical Thermal Release is pre-
wired with 0.5m halogen free low
smoke and fume cabling to Control
Modes 5 and 6.
A Manual test switch fitted on the
ETR allows periodic operation of
damper simulating actual fail-safe
release under smoke/fire conditions.

Smoke/Shield and Vent/Shield
PTC™ Dampers and associated
Control Modes 5 and 6 are
available without the ETR where
thermal operation is not required.

If integrating this unit with an Actionpac
damper control system (LNS or EM)
please refer to the relevant catalogue
and specific project details.

For non ETR applications refer to
specific product label on Mode, prior
to electrical connections.

Содержание Smoke/Shield PTC

Страница 1: ...lication and Wiring 5 Hot Shield PTC and Hot Shield Vent PTC Damper Installation and Dimensional Data Application and Wiring 6 Hot Shield PTC and Hot Shield Vent PTC Dimensional Data 7 Hot Shield PTC and Hot Shield Vent PTC Multiple Assembles 7 Smoke Shield PTC Vent Shield PTC Hot Shield PTC and Hot Shield Vent PTC Troubleshooting 8 Smoke Shield PTC Modes 1 5 6 fail safe spring close with manual o...

Страница 2: ...tallation frames are delivered to site as a complete assembly with the appropriate PTC damper fitted therein The damper shall be installed centrally in the thickness of a brickwork or concrete surrounding wall or floor or in the case of thick walls or floors so that the centre line of the frame is at least 50mm but not more than 75mm away from the nearest face of the wall or floor in which the ass...

Страница 3: ... Three position 180 Pivotable Control Mode Control Mode Dimensional Data 2 Fit Control Mode Remove transit plate from damper shroud and discard Slide the interface and mode assembly into the shroud having ensured that the slots in the interface case and the drive coupling are in line Push the assembly fully home until the spring retaining pin engages through the location hole in the shroud snaploc...

Страница 4: ...ess installations the ETR should be fitted onto the damper spigot not casing above the damper shroud and in accordance with these fitting instructions The damper should be manually reset and released using the winder provided to ensure that correct mechanical operation is achievable It is possible to mechanically lock open the Smoke Shield PTC damper to allow air to pass through it by using the wi...

Страница 5: ...s Connect 24V via a safety isolating transformer Vent Shield PTC dampers and associated control modes 5 and 6 are reverse acting with spring action opening Mode 6 230V System Power On Damper motors open Power Off Spring closure or via Electrical Thermal Release External mechanical position indicator with pointer Release Time 16 secs Reset Time 1c secs To isolate from main power supply the system m...

Страница 6: ...urposes Please contact our Customer Service Office for details when incorporating thickened fire rated ductwork 411 421 161 27 191 Damper Installation and Control Mode Fitting Series 2501 Hot Shield PTC Application and Wiring 1 2 1 2 3 4 VOLT FREE CONTACT CLOSED WHEN DAMPER RELEASED VOLT FREE CONTACT CLOSED WHEN DAMPER RESET A C D C 24V 50 60 Hz 10 V A 7 2 W 30 50 C CONTINUOUS A C 250V 6 3 A SUPPL...

Страница 7: ...mpers with duct diameters between 100mm diameter 150mm diameter will have nominal damper size of 200mm diameter Dampers with duct diameters between 151mm diameter 982mm diameter will have nominal damper size 50mm Dampers with a nominal damper size between 983mm diameter 1000mm diameter please refer to Customer Service Office 7 Always refer to Customer Service Office for dimensional data when incor...

Страница 8: ...rrectly wired The ETL cables have been damaged or tampered with Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface The damper is damaged or poorly installed The retaining pin in the interface is not protruding through the location hole in the shroud Foreign matter is impeding blade movement Location plate omitted ...

Отзывы:

Похожие инструкции для Smoke/Shield PTC