background image

BLUE

N

L

1

BROWN

1

2

3

4

VOLT FREE CONTACT

CLOSED WHEN

DAMPER RELEASED

VOLT FREE CONTACT

CLOSED WHEN

DAMPER RESET

SUPPLY

230V A.C 50/60 Hz

A.C. 230V

50 / 60 Hz

12.5 V A

8 / 3 W

–30...+50 

°

C

CONTINUOUS 

A.C. 
250V
6(3)A

M

6

Hot/Shield PTC™                Hot/Shield Vent PTC™ 

Damper 
Drive Shroud

Snap

lock™

Retaining Pin

Transit
Plate

Ductwork

Hot/Shield,
Hot/Shield Vent 
Damper

Control Mode 5/6 
housed in thermally 
insulated enclosure

Dimensional Data

Install the Hot/Shield PTC™ Damper
(complete with factory fitted damper
shroud and transit plate) into the
structure, connect and fit ductwork to
damper spigots. Remove transit plate
and discard. Slide the 

snap

lock™

drive interface into the damper drive

shroud, 

snap

lock™ into position.

(See page 2.)

(Care must be taken when back filling
to ensure that the snaplock™
retaining pin location hole and the
entry slot of the damper drive shroud
is clear of builders work debris).

The above dimensional data is for
guide/general arrangement purposes.

Please contact our Customer
Service Office for details when
incorporating thickened fire rated
ductwork.

411

421

161

27

191

Damper Installation and Control
Mode Fitting

Series 2501

Hot/Shield PTC Application and Wiring

+

1

2

1

2

3

4

VOLT FREE CONTACT

CLOSED WHEN

DAMPER RELEASED

VOLT FREE CONTACT

CLOSED WHEN

DAMPER RESET

A.C./D.C.24V

50 / 60 Hz

10 V A

7/2 W

–30...+50 

°

C

CONTINUOUS

A.C. 
250V
6(3)A

SUPPLY

24V A.C. or D.C.

M

Mode HM5

(24V System)

Power On – Damper motors open.
Power Off – Spring closure.

Cable specification:
Si HF Low Smoke and Fume,
Halogen Free, to IEC 754-1.
Conforming to 73/23/EEC directive.

Release Time 

16 secs.

Reset Time 

≈ 

140 secs.

(Connect 24V via a safety isolating transformer.)

Mode HM6

(230V System)

Power On – Damper motors open.
Power Off – Spring closure.

Cable specification:
Si HF Low Smoke and Fume,
Halogen Free, to IEC 754-1.
Conforming to 73/23/EEC directive.

Release Time 

16 secs.

Reset Time 

≈ 

140 secs.

(To isolate from main power supply, the system
must incorporate a device which disconnects the
phase conductors, with a least 3mm contact gap.)

Hot/Shield Vent PTC™ Dampers and
associated Control Modes are reverse
action with spring operation

Содержание Smoke/Shield PTC

Страница 1: ...lication and Wiring 5 Hot Shield PTC and Hot Shield Vent PTC Damper Installation and Dimensional Data Application and Wiring 6 Hot Shield PTC and Hot Shield Vent PTC Dimensional Data 7 Hot Shield PTC and Hot Shield Vent PTC Multiple Assembles 7 Smoke Shield PTC Vent Shield PTC Hot Shield PTC and Hot Shield Vent PTC Troubleshooting 8 Smoke Shield PTC Modes 1 5 6 fail safe spring close with manual o...

Страница 2: ...tallation frames are delivered to site as a complete assembly with the appropriate PTC damper fitted therein The damper shall be installed centrally in the thickness of a brickwork or concrete surrounding wall or floor or in the case of thick walls or floors so that the centre line of the frame is at least 50mm but not more than 75mm away from the nearest face of the wall or floor in which the ass...

Страница 3: ... Three position 180 Pivotable Control Mode Control Mode Dimensional Data 2 Fit Control Mode Remove transit plate from damper shroud and discard Slide the interface and mode assembly into the shroud having ensured that the slots in the interface case and the drive coupling are in line Push the assembly fully home until the spring retaining pin engages through the location hole in the shroud snaploc...

Страница 4: ...ess installations the ETR should be fitted onto the damper spigot not casing above the damper shroud and in accordance with these fitting instructions The damper should be manually reset and released using the winder provided to ensure that correct mechanical operation is achievable It is possible to mechanically lock open the Smoke Shield PTC damper to allow air to pass through it by using the wi...

Страница 5: ...s Connect 24V via a safety isolating transformer Vent Shield PTC dampers and associated control modes 5 and 6 are reverse acting with spring action opening Mode 6 230V System Power On Damper motors open Power Off Spring closure or via Electrical Thermal Release External mechanical position indicator with pointer Release Time 16 secs Reset Time 1c secs To isolate from main power supply the system m...

Страница 6: ...urposes Please contact our Customer Service Office for details when incorporating thickened fire rated ductwork 411 421 161 27 191 Damper Installation and Control Mode Fitting Series 2501 Hot Shield PTC Application and Wiring 1 2 1 2 3 4 VOLT FREE CONTACT CLOSED WHEN DAMPER RELEASED VOLT FREE CONTACT CLOSED WHEN DAMPER RESET A C D C 24V 50 60 Hz 10 V A 7 2 W 30 50 C CONTINUOUS A C 250V 6 3 A SUPPL...

Страница 7: ...mpers with duct diameters between 100mm diameter 150mm diameter will have nominal damper size of 200mm diameter Dampers with duct diameters between 151mm diameter 982mm diameter will have nominal damper size 50mm Dampers with a nominal damper size between 983mm diameter 1000mm diameter please refer to Customer Service Office 7 Always refer to Customer Service Office for dimensional data when incor...

Страница 8: ...rrectly wired The ETL cables have been damaged or tampered with Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface The damper is damaged or poorly installed The retaining pin in the interface is not protruding through the location hole in the shroud Foreign matter is impeding blade movement Location plate omitted ...

Отзывы: