Installation and Commissioning Guide - MultiElite 2 Split System
Doc. No. 9590-5009
Ver. 1 211221
20
Installation and Commissioning Guide
Multi Split System
CAUTION
If the outdoor unit is installed at a higher position than the indoor unit , it is recommended that the vertical suction risers not
be upsized. Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below 7.62
m/s, oil return will be decreased. An oil trap should be installed every 6m of vertical suction line riser.
Oil Trap
Gas Piping
Outdoor Unit
Indoor Unit
Liquid
Piping
6m
6m