Installation and Commissioning Guide - MultiElite 2 Split System
Doc. No. 9590-5009
Ver. 1 211221
19
Installation and Commissioning Guide
Multi Split System
9. Mount the Valve cover back.
Total Installed Refrigerant
Charge Label
CAUTION
If the indoor unit is installed at a higher position than the outdoor unit , there is chance that oil may flow into the
compressor. This may cause liquid compression or deterioration of oil return. Use oil traps in the gas piping to prevent this.
An oil trap should be installed every 10m in the vertical suction line riser.
Oil Trap
Gas Piping
Indoor Unit
Liquid
Piping
Outdoor Unit
10m
10m