Installation and Commissioning Guide - MultiElite 2 Split System
Doc. No. 9590-5009
Ver. 1 211221
11
Installation and Commissioning Guide
Multi Split System
09. Outdoor Unit Installation
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
O
utdo
or
U
ni
t
In
sta
lla
tio
n
Installation Instructions – Outdoor unit
SPECIAL CONSIDERATIONS FOR EXTREME
WEATHER
600mm ab
ove
300mm fr
om
back wall
2000mm
in fr
ont
600mm
on right
300mm
on left
09.01. Outdoor Unit Installation Instructions
Step 1. Select Installation Location
Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help
you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
1. Meets all spatial requirements shown in Installation Space Requirements above.
2. Good air circulation and ventilation
3. Firm and solid: the location can support the unit and will not vibrate
4. Noise from the unit will not disturb others
5. Protected from prolonged periods of direct sunlight or rain
6. Where snowfall is anticipated, take appropriate measures to prevent ice buildup and coil damage.
DO NOT install unit in the following locations:
1. Near an obstacle that will block air inlets and outlets
2. Near a public street, crowded areas, or where noise from the unit will disturb others
3. Near animals or plants that will be harmed by hot air discharge
4. Near any source of combustible gas
5. In a location that is exposed to large amounts of dust
6. In a location exposed to a excessive amounts of salty air