LIFTING THE UNIT

Always observe WH&S regulations for safe & secure lifting 

practices in order to prevent physical injury.  

Suggested lifting procedures are outlined in the next page 

as reference guide to safely lift & transport the unit, however, 

these does not over rule the industry WH&S practices.   

LOCATION

This unit is intended for indoor installation only. 

It is highly 

recommended that this indoor unit and accessories, 

particularly zone barrels, be mounted in the roof cavity.

Mount the unit in a stable and rigid support wherein the 

weight is properly distributed, such as roof joist and rafters. 

Take into consideration the minimum service access 

clearances  provided in the unit drawings. 

Locate the indoor unit away from the areas where noise 

is a critical factor. Use rubber mounting pad (not supplied) 

in order to minimize the transfer of noise & vibration into 

building structures. 

A hanging bracket assembly & rubber grommet (optional on 

other units) are also provided to secure the indoor unit into 

the roof rafters. This installation configuration is most suitable 

for installation that require the unit to be rigidly secured up 

from the roof joist.   

   

CONDENSATE & SAFETY TRAY DRAINAGE

An integrated safety drain tray is provided as a standard 

inclusion to your indoor unit in order to reduce the potential of 

condensate damage to the roof. Drain Kit (optional on some 

units) is provided for the condensate drain to be externally 

trapped from the indoor unit. Suggested condensate 

and safety tray drainage instructions are provided at the 

proceeding page for your reference. 

SUPPLY AIR & RETURN AIR DUCT

The indoor unit is supplied with duct flange as standard in 

order to facilitate the system’s duct connection into the unit. 

Supply and return air duct works must be adequately sized to 

meet the system’s air flow and static pressure requirements. 

Refer to the unit drawing for supply air and return air duct 

dimensions, specific to your requirement.

NOTE: Fit a flexible duct connection in between the unit 

and the duct system, where noise & vibration is a critical 

consideration.

RETURN AIR FILTER 

Air filters must be provided in the return air side of the unit 

in order to maintain the efficiency and prolong the operation 

of the unit. These are also paramount in order to  satisfy 

requirement for a clean & hygienic room condition. Air filters 

must be placed in an easily accessible location for service 

and maintenance.

NOTES:

    1. Air filters are not supplied with the unit as individual air 

        filtration requirements are varied.

    2. Ensure that filters are cleaned / replaced regularly.

SUPPLY AIR & RETURN AIR DUCT (OPTIONAL)

Supply Air plenums and Duct Plates (twin-spigot) are 

available in order to facilitate your duct system connection to 

the indoor unit. The supply air plenums come in 1-way, 2-way 

and 3-way options, which offer a wider solutions to your 

different air distribution requirements.

SPLIT FAN COIL SYSTEM (OPTIONAL ERQ4-19AS)

The Actron Air innovative 2-piece fan coil system provides 

a solution to your difficult and tight roof space installation 

requirement. This versatile system has a separate fan and 

coil sections. Each of the compact and lightweight section 

is simply installed in two separate locations and joined by 

flexible duct system. Air ducts are attached to each section  

of the split fan coil by both of the supply air plenum and the 

twin spigot duct plate.

FAN COIL w/ VERTICAL DISCHARGE (OPTIONAL)

An upright Fan Coil with vertical supply air discharge is 

also available wherein installation applications require the 

placement of the unit down in a closet, basement or garage. 

Please refer to the Technical Catalogue of your indoor unit 

for dimensions, installation details and specifications.

FIELD PIPE CONNECTIONS

Specifications and installation requirements for field 

pipe connections are contained in the Installation & 

Commissioning Guide of the outdoor unit that matches 

your indoor unit. Please refer to this guide and thoroughly 

understand the procedures for safe and correct indoor and 

outdoor connection. 

ELECTRICAL FIELD CONNECTION

The power supply and control communication data to the 

indoor unit are supplied via the outdoor unit. Please refer 

to the wiring diagram supplied with the outdoor unit for 

specifications. 

All electrical work must be performed by a licensed 

electrician and must conform with the wiring diagram and all 

relevant electrical authorities.   

INSTALLATION INSTRUCTIONS

The installation instructions provided below are intended as a guide only and does not supersede the relevant council, 

state and federal codes, regulations and building code standards. Compliance and consultation with the authorities 

having jurisdiction with the installation of this equipment is the responsibility of the installer. Actron Air will not be held 

liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit 

Installation & Commissioning Guide for further information and details. 

Содержание ESP PLATINUM ERQ2-14AS

Страница 1: ... and or reproduction are prohibited without written consent from Actron Air Please Read This Guide Congratulations on your purchase of an Actron Air air conditioning unit This unit has been designed and manufactured with the highest quality standard in mind Please read this guide thoroughly and keep it near the unit for future reference INDOOR UNITS ESP PLATINUM ERQ2 14AS ERQ3 17AS ERQ4 19AS ESP P...

Страница 2: ...ety instructions in this literature and all warning labels that are attached to the equipment 2 Prevailing WH S regulations must be observed and will take precedence to the safety instructions contained on this manual Safe work practices and environment must be the paramount importance in the performance of all the service procedures 3 Ensure that unit installation complies with relevant council r...

Страница 3: ...o change without notice Copyright 2017 Actron Engineering Pty Ltd Page 3 of 16 COMPONENTS OVERVIEW INDOOR UNIT COMPONENTS OVERVIEW Indoor Unit EC Motor ID Fans ID Coil 8Z VAQ Module Lid Control Panel Indoor Control Panel SRD175C SRD175E DATA DIGITAL SCROLL COMPRESSOR DUCTED UNIT Indoor Unit Control Board EMC Filter ...

Страница 4: ...d the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION STACKING OF UNITS ONE IN FRONT OF THE OTHER DISTANCE BET A B SIDE BY SIDE DISTANCE BET A C DUCT WORK 800 mm HEIGHT CLEARANCE 340 B D C A DUCT WORK DUCT WORK 800 mm SERVICE CLEARAN...

Страница 5: ...units or between the unit and the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION OVERALL NOMINAL DIMENSION H x W x D 435 x 1420 x 680 SUPPLY DUCT H x W 300 x 715 RETURN DUCT 360 x 1140 DRAIN CONNECTION 20mm OD TOP VIEW FRONT VIEW SI...

Страница 6: ...Y PLENUM 2 WAY SUPPLY PLENUM TWIN SPIGOT DUCT PLATE 1 WAY SUPPLY PLENUM UNIT FEATURES flexible ducting Ducting is attached to each section by either a 1 2 or 3 way EASY FIT supply plenum or a twin spigot duct plate these can be fitted to either side of each section ADD ON COOLING is simply achieved by fitting only the coil section into an existing ventilation system Note External static pressure i...

Страница 7: ...nt for a clean hygienic room condition Air filters must be placed in an easily accessible location for service and maintenance NOTES 1 Air filters are not supplied with the unit as individual air filtration requirements are varied 2 Ensure that filters are cleaned replaced regularly SUPPLY AIR RETURN AIR DUCT OPTIONAL Supply Air plenums and Duct Plates twin spigot are available in order to facilit...

Страница 8: ...riable Refrigeration Capacity Multiple Speed Outdoor Fans SPECIFICATION SUMMARY OUTDOOR UNIT MODEL SRD INDOOR UNIT MODEL SRD R410A DIGITAL SCROLL COMPRESSOR ESP SPLIT DUCTED UNIT 624 675 100 100 100 675 38 38 Fig 2 ELECTRICAL PANEL END INSERT FORKLIFT TINES HERE INSERT FORKLIFT TINES HERE SRD175C SRD175E ELECTION DATA DIGITAL SCROLL SPLIT DUCTED UNIT SRD175C SRD175E ECTION DATA SPECIFICATION SUMMA...

Страница 9: ... TRAY DOES NOT OVERFLOW INDOOR COIL RETURN AIR INDOOR COIL CONDENSATE DRAIN MUST BE RUN SEPERATLY FROM THE SAFETY TRAY DRAIN SAFETY TRAY DRAIN CONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PI...

Страница 10: ...ONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL BARRELS MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS Duct Duct Zone Barrel Damper Motor on Top of the Zone Barrel TYPE 10 250 mm PART NUMBER ZB 10 250 IN...

Страница 11: ...REEN WIRE REMOVED ON INDOOR UNIT SCREEN FOIL CLAMPED TO P CLIP ON OUTDOOR UNIT POWER DATA YELLOW CAT5E CABLE POWER ONLY YELLOW CAT5E CABLE MASTER SECONDARY OPTIONAL WiFi WiFi RF RF MODULATION ZONING QUEIB DATA ZONE 8 ZONE 7 ZONE 6 ZONE 5 ZONE 4 ZONE 3 ZONE 2 ZONE 1 TO ZONE 2 8 240V MAINS ZONE MOTOR ZONE CONTROL 1 REMOTE SENSOR 1 LOG RJ45 SOCKETS FOR ACTRON AIR CAT5E SPEC CABLES ONLY REFER TO QUE C...

Страница 12: ...lip OUTDOOR UNIT TO OUTDOOR PCB MODEL R 410A CAUTION PLEASE THERE IS NO GAS PRESSURE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S TRALIAN M A D E A U STRALIAN OW N E D R 410A 1 DIAGRAM SHOWING SCREEN FOIL CLAMPING Metal P Clip Electrical Panel 2 CO...

Страница 13: ...MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS MOUNTING SCREWS ITEM PART NUMBER 7 METER CABLE 4070 004 ZONE MOTOR ONLY TRANSFORMER ONLY ZM 24V 2045 046 20 METER CABLE 4070 007 2 WAY RJ45 JOINER 2045 121 3 WAY RJ45 JOINER 4070 008 ZONE OPTION 2 1 5V AAA 1 5V AAA 1 5V AAA 1 5V ...

Страница 14: ...ng Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility ...

Страница 15: ...ESCRIPTION PART NUMBER QUANTITY QUANTITY QUANTITY 1 EC ID Fan 2520 333 1 1 2 EC ID Fan 2520 334 1 3 Indoor Coil Assembly 1040 156 1 4 Indoor Coil Assembly 1040 254 1 5 Indoor Coil Assembly 1040 177 1 6 Coil Piston 4540 088 1 7 Coil Piston 4540 098 1 8 Coil Piston 4540 128 1 9 ID Control Board AFS QUEIB1 1 2020 154 1 1 1 10 Zone Module 8Z VAQ 1 1 1 11 Filter Board 4080 013 1 1 1 12 Yellow Cat5e Cab...

Страница 16: ...Ltd ABN 34 002 767 240 HEAD OFFICE SYDNEY AUSTRALIA Printed in Australia Part No 0525 052 Rev No 4 0 180302 1800 119 229 actronair com au Copyright 2017 Actron Engineering Pty Ltd Refrigerant Trading Authorisation No AU06394 ...

Отзывы: