COMPONENTS OVERVIEW
INDOOR UNIT COMPONENTS OVERVIEW
Indoor
Unit
EC Motor
ID Fans
ID Coil
8Z-VAQ Module
Lid - Control Panel
Indoor
Control Panel
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Indoor Unit
Control Board
EMC Filter