ACTpro 3000 Operating Instructions
Firmware Version 1.24
17
Door Settings
The
Door Settings
menu allows the installer to access a number of different configuration menus
controlling different aspects of the selected door. The door for which the settings are to be changed
is first selected using the
0
key and then the
✔
key is pressed to enter the menu.
The
0
key is used to select the required option or setting which is changed using the
✔
key.
OPERATION
This menu allows the installer to select or de-select a number of options relating to the default
operation of the door.
•
The
Push Button
option allows the relay to be activated when the external push-button contact
is closed. This option is selected by default.
•
The
Locksaver
(anti-tailgate) option truncates the relay timer when the door opens. This
ensures that the door will be locked as soon as it closes even if a very long relay time is
programmed. This also prevents overheating of the lock solenoid.
•
The
Chime
option momentarily energizes the buzzer output whenever the door contact is seen
to open. The onboard buzzer also makes a chime sound.
•
The
Guest Button
option activates the AUX relay for the programmed duration when the
key
or
✓
key on an externally connected keypad is pressed.
•
The
Exit Always
option allows the holder of a valid enabled card to exit at all times irrespective
of the configured timezones.
•
The
Interlock
option prevents the door being opened when the AUX input is active. OP3
activates when the door is open or the door relay is active.
•
The
Silent
option prevents the door buzzer from sounding when access is granted or denied.
•
The
Exit PIR
option will keep the door open while the external push-button contact is closed.
This allows a PIR to be used as the exit switch.
•
The
Failsafe
option sets the door relay to be normally energised. This means that the door will
open if the power supply to the controller fails.
•
The
Toggle Relay
option allows the door to be toggled open or closed by users with the Toggle
Relay option enabled.
•
Setting the
Monitor Arming
option indicates that the AUX input is connected to an external
alarm panel and is monitoring the alarm state. When the AUX input is low, the panel is armed
and access is denied to users. This option is only valid if the Arm Intruder Alarm Option is also
set.
ALARMS
This menu allows the installer to enable or disable a number of alarm events that can be generated
by the controller:
•
The
Door Forced
alarm occurs when the door contact opens without the relay having been
energized. The AUX relay is activated until a valid card is presented.
•
The
Door Ajar
alarm occurs when the door has remained open for longer than the duration
programmed into the door ajar timer. The AUX relay is activated while the door remains open.
•
The
Duress
alarm occurs whenever a duress code is entered during Pin & Card operation. The
duress code is the PIN code for that user with the last digit advanced by one.
•
The
Door Open
alarm activates the AUX relay whenever the door is open.
•
The
Access Granted
alarm activates the AUX relay for the programmed time whenever a valid
card is presented at an entry reader.
•
The
Exit Granted
alarm activates the AUX relay for the programmed duration whenever a
valid card is presented at an exit reader.
•
The
Access Denied
alarm activates the AUX relay for the programmed duration whenever an
invalid card is presented to an entry reader.